Explicit Messaging Chapter 4
Follow these steps to configure a message.
1. Choose the appropriate parameters in the Message
Configuration window.
Parameter
Choice
Message Type
Choose message type CIP Generic.
Service Type
Read: Select service type Get Attribute Single
Write: Select service type Set Attribute Single
Instance
Refer to
for the CIP Instance of the data table you are
requesting to read. In this example, the power monitor’s Voltage, Amp,
and Frequency data table is instance 14.
Class
4
Attribute
3
Destination
Get Attribute Single - This is the controller tag in which to store the
data being read.
Source Element
Set Attribute Single - Refer to
for the address of the
specific data table address you’re writing to.
Source Length
Set Attribute Single - This is the number of elements of the source
element, to be written to the power monitor.