Appendix A Powermonitor 1000 Data Tables
Log Request Table Parameters
CSP File No.
N17
CIP Instance
10
No. of Elements
11
No. of Words
11
Data Type
Integer
Data Access
Read/Write
Log Request Table
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0
40701
Selected Log
0
0…5
•
•
•
•
•
Selects the log that information is
returned from. Once a single request
has been made the auto return feature
will bring back successive records
each time the log is read. Some logs
support individual record requests.
1 = Unit Status Log
2 = Min/Max Log
3 = Energy Log
4 = Load Factor Log
5 = Time of Use Log kWh
6 = Time of Use Log kVAR
7 = Time of Use Log kVA
If your catalog number does not
support the requested log item the
power monitor will ignore the request.
1
40702
Chronology of
Auto Return
Data
1
0…1
•
•
•
•
•
The date chronology of the returned
records.
0 = Reverse direction
1 = Forward direction
2
40703
The Min/Max
record to be
returned
0
0…35
0…31
0…15
•
•
•
Selects the Min/Max record number
to be returned. See the table for
Min/Max record list.
0 = Use incremental return and the
chronology selected.
EM3 = 1…35
TR2 = 1…31
TR1 = 1…15
3
40704
Number of Unit
Status Records
-
1…50
•
•
•
•
•
On a read of this table the value of this
parameter is the number of Unit
Status Records available. This log is
only returned using the incremental
return method.