Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 74

74
Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
3
30507-8
Demand PF
-100.0…+100.0
•
•
The average demand for PF during
the last demand period.
4
30509-10
Projected kWatt
Demand
+/- 0.000…9,999,999
•
•
The projected total real power for
the current period.
5
30511-12
Projected kVAR
Demand
+/- 0.000…9,999,999
•
•
The projected total reactive power
for the current period.
6
30513-14
Projected kVA
Demand
0.000…9,999,999
•
•
The projected total apparent power
for the current period.
7
30515-16
Elapsed Demand
Period Time
0.00…99.99
•
•
The amount of time that has
elapsed during the current period.
8
30517-18
Metering Iteration 0…9,999,999
•
•
Increments by 1 for each new
metering calculation.
Demand Results
Element
No.
Modbus
Address
Element Name
Range
TR1
TR2
EM1
EM2
EM3
Description
Unit Status Log Results Parameters
CSP File No.
N25
CIP Instance
18
Applies to
All models
No. of Elements
13
No. of Words
13
Data Type
Integer
Data Access
Read
Unit Status Log Results
Element
No.
Modbus
Address
Element Name
Range
Description
0
30601
Status Record Internal
Identifier
1…50
Used to verify record sequence when returning multiple
records.
1
30602
Timestamp Year of record
-
The year when the record was recorded.
2
30603
Timestamp Month/Day
-
The month and day when the record was recorded.
3
30604
Timestamp Hour/Minute
-
The hour and minute when the record was recorded.
4
30605
Timestamp
Seconds/Hundredths
-
The seconds and hundredths when the record was recorded.
5
30606
Status Event Type
0…512
Indicates the type of status event that has occurred.
6
30607
General Code
0…4096
Indicates general information about the status event.
7
30608
Information Code
0…256
Indicates specific information about the status event.