Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 51

Publication 1408-UM001B-EN-P - May 2008
51
Powermonitor 1000 Data Tables Appendix A
Serial RS-485 Port Configuration Parameters
CSP File No.
N12
CIP Instance
5
Applies to
All models
No. of Elements
9
No. of Words
9
Data Type
Integer
Data Access
Read/Write
Serial RS-485 Port Configuration
Element
No.
Modbus
Address
Element Name
Default
Value
Range
Description
0
40201
Password
0
0…9999
When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate
password table should be used. Returns -1 on a read.
1
40202
Protocol Setting
1
0…3
The protocol selection for communications.
0 = DF1 Half Duplex Slave
1 = DF1 Full Duplex
2 = Modbus RTU Slave
3 = Auto Sense
4 = DH485
2
40203
Serial Delay
2
(10 ms)
1…15
The setting times 5 = milliseconds that the unit waits before
responding to a communication request. Useful for consistent
communications and slow devices.
3
40204
Baud Rate
5
0…6
The serial communications baud rate.
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38,400
6 = 57,600
4
40205
DF1, DH485,
Modbus Address
Device
ID,
31 for
DH485
1…247
(DF1,
Modbus)
0…31
(DH485)
During production the Device ID is printed on the nameplate. This ID
then becomes the default address for DF1 and Modbus.