Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
5
40111-12
Daylight
Savings
Month/Week
/Day Start
030201
March,
2nd,
Sunday
10101…
120507
•
•
•
•
•
This is the day that the power monitor will
add an hour to the time. This feature also
looks at Ethernet SNTP offset and corrects
for Daylight Savings.
Example: 040107 = April/1st week/Sunday
Month Settings:
01 = January…12 = December
Week Settings:
01 = 1st week…05 = Last Week
Day of the Week Settings:
01 = Sunday…07 = Saturday
6
40113-14
Hour of Day
Start
2
0…23
•
•
•
•
•
The hour of day the daylight savings
adjustment should be made to add an
hour.
7
40115-16
Return from
Daylight
Savings
Month/Week
/Day
110101
November,
1st,
Sunday
10101…
120507
•
•
•
•
•
This is the day that the power monitor will
subtract an hour from the time. This
feature also looks at Ethernet SNTP offset
and corrects for the return from Daylight
Savings.
Month Settings:
01 = January…12 = December
Week Settings:
01 = 1st week…05 = Last Week
Day of the Week Settings:
01 = Sunday…07 = Saturday
8
40117-18
Hour of Day
End
2
0…23
•
•
•
•
•
The hour of day the daylight savings
adjustment should be made to subtract an
hour.
9
40119-20
KYZ Solid
State Output
Parameter
0
0…5
•
•
•
The parameter selected will pulse the KYZ
output at a rate that equals the parameter
value divided by KYZ scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd (EM2 and EM3 Only)
4 = VARh Rev (EM2 and EM3 Only)
5 = Vah (EM2 and EM3 Only)
10
40121-22
KYZ Solid
State Output
Scale
1,000
1…
100,000
•
•
•
The KYZ output parameter divided by the
scale is the output pulse rate. Example:
Wh is selected for the parameter and
1,000 is the scale value. The output is
pulsed every kWh.
Advanced Configuration
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description