Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 47

Publication 1408-UM001B-EN-P - May 2008
47
Powermonitor 1000 Data Tables Appendix A
Advanced Configuration Parameters
CSP File No.
F11
CIP Instance
4
No. of Elements
22
No. of Words
44
Data Type
Float
Data Access
Read/Write
Advanced Configuration
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
TR
1
TR
2
EM
1
EM
2
EM
3
Description
0
40101-2
Password
0
0…9999
•
•
•
•
•
When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
1
40103-4
New
Password
0
0…9999
•
•
•
•
•
This becomes the new password when the
proper the configuration password entry
has been made and this parameter is
greater than (-1).
2
40105-5
Metering
Result
Averaging
1
0…1
•
•
•
•
•
The metering results for volts, amps,
power and frequency is averaged over 8
cycles of data to provide a steady output
reading.
0 = Off
1 = On
3
40107-8
Log Status
Input
Changes
0
0…1
•
•
•
•
•
0 = Disable recording of status input
changes into the status log.
1 = Enable recording of status input
changes into the status log.
4
40109-10
Use Daylight
Savings
Correction
0
0…1
•
•
•
•
•
0 = Disable Daylight Savings
1 = Enable Daylight Savings