6 voltage connections, Figure 2-9 figure 2-9a – West Control Solutions MRC 9000 User Manual
Page 30
Section 2
2-11
Edition 3
Rev G
2.3.6 VOLTAGE CONNECTIONS
Note: Up to four Input Boards may be present; stacked 4 high. Input Board 1 is the bottom board. Two
versions of Input Board s may be found, see Figure 2-9 and Figure 2-9A.
Input Board 1 is used for Input 1 and, if equipped, Input 2. Input Board 2 is used for Input 3 and Input 4, if
equipped. Input Board 3 is for Input 5 and Input 6. Input Board 4 is for Input 7 and Input 8.
Connect positive (+) leg to terminal 1 and negative (-) leg to terminal 2 on the Input Board(s) to be volt input.
Terminal block 1 (TB1) is Input 1, 3,5 and 7 and terminal block 2 (TB2) is Input 2, 4, 6, and 8.
NOTE: INPUT CONDITIONING JUMPERS MUST BE POSITIONED AS SHOWN FOR VOLT INPUT IN EITHER
FIGURE 2-8 OR 2-8A DEPENDING ON WHICH CIRCUIT BOARD IS FITTED. ALSO NOTE: THERE IS NO
SENSOR BREAK DETECTION FOR ZERO BASED VOLT INPUTS. EXAMPLE: 0-5V.
FIGURE 2-9
FIGURE 2-9A
JU1
JU11
U6
JU7
+
+
-
-
1
1
TB1
TB2
JU2
JU5
JU12
JU4
JU8
JU15
JU16
LOW
VOLT
INPUT
SPAN
NARROW
0/25 mV
WIDE
0/100mV
INPUT 2, 4, 6, 8
JU8
INPUT 1, 3, 5, 7
JU7
JU3
0/10V
0/5V
0/1V &mV
JU6
0/10V
0/5V
0/1V &mV
JU3
JU6
NOTE: Terminal Block 1, Terminal 1 is on the RIGHT,
Terminal Block 2, Terminal 1 is on the LEFT.
LOW
VOLT
INPUT
SPAN
NARROW
0/25 mV
WIDE
0/100mV
INPUT 2, 4, 6, 8
JU8
INPUT 1, 3, 5, 7
JU7
JU3
0/10V
0/5V
0/1V &mV
JU6
0/10V
0/5V
0/1V &mV
U1
+
+
-
-
1
1
TB1
TB2
JU5
JU6
JU16
JU7
JU3
JU2
JU15
JU8