beautypg.com

West Control Solutions MRC 9000 User Manual

Page 271

background image

Edition 3

Rev G

Section 14

14-3

When Segs Done - Profiles may be joined together to increase the number of segments or to
make use of common profiling sequences. When all segments in the initiated profile have been
executed the specified number of loops, the WHEN SEGS DONE parameter can “join” another
profile. The instrument retains which profile was initiated, as well as which profile is currently
running or “joined. When one of the profiles ends with “END”, processing will revert back to the
initial profile where, if Profile Loop Count is greater than one, the unit will proceed through the
initial profile or terminate as specified in the initial profile.

18. Press the SCROLL key to advance to the next parameter, Pxx PROFILE LOOP COUNT. Selections
0-9999. Press the MOD key to change, then press the LEFT/SCROLL, UP/DOWN as required to desired
loop count, then press the ENTER key.

Profile Loop Count - The profile loop count will appear in all profiles but only the initial profile will
use the loop count. At the end of a profile the profile loop count will determine if the profile will
terminate or proceed through the profile again.

19. Press the SCROLL key to advance to the next parameter, Pxx END ACTION. Selections are: OFF,
EVENTS OFF (Unit turns all outputs off or 0% including the events; OFF, EVENTS SAME (Unit turns
control outputs off or 0% but keeps the events in the same condition they were - on remain on; off remain
off); or CONTROL, EVENTS SAME (Unit reverts to control with the events the same). Press the MOD
key to change, then UP/DOWN as required to desired choice, then press the ENTER key.

20. Press the SCROLL key to advance to the next parameter, Pxx ABORT ACTION. Selections are: OFF,
EVENTS OFF (Unit turns all outputs off or 0% including the events; OFF, EVENTS SAME (Unit turns
control outputs off or 0% but keeps the events in the same condition they were - on remain on; off remain
off); or CONTROL, EVENTS SAME (Unit reverts to control with the events the same). Press the MOD
key to change, then UP/DOWN as required to desired choice, then press the ENTER key.

21. Press the SCROLL key to advance to the next parameter, Pxx POWERFAIL ACTION. Selections are:
CONTINUE; HOLD; ABORT; or RESTART. Press the MOD key to change, then UP/DOWN as required to
desired choice, then press the ENTER key.

22. Press the SCROLL key to advance to the next parameter, Pxx RECOVERY TIME LIMIT, displayed as
hhh:mm:ss, where h is hours, m is minutes, and s is seconds. Press the MOD key to change, then UP/
DOWN to desired number, then press the ENTER key. NOTE: This procedure will need to be performed
for each segment of time; hours, minutes and seconds.

23. Press the SCROLL key to advance to the next parameter, Pxx RECOVERY ACTION. Selections are
CONTINUE, HOLD, ABORT, or RESTART. Press the MOD key to change, then LEFT/SCROLL, UP/
DOWN as required to desired choice, then press the ENTER key.

Power Failure - If power fails the unit will respond based upon the parameters specified by
POWER FAIL ACTION or RECOVERY ACTION, depending on the parameter specified by
RECOVERY TIME LIMIT. During profiling, the current time is saved in non-cleared memory every
second. During initialization, the last time saved while the profile was running is compared to the
current time. If the unit was off for a time period greater than specified by RECOVERY TIME
LIMIT, RECOVERY ACTION parameter applies. If the period of time is less than the RECOVERY
TIME LIMIT, POWER FAIL ACTION parameter applies.
POWER FAIL ACTION and RECOVERY ACTION specify what shall happen based upon the
choice selection made:
CONTINUE requires no action, the profile will continue at the point the profile was interrupted.
HOLD will place the profile in the HOLD condition and stop in the current segment (ramp or dwell)
with the time remaining for the segment held at the last value before placed into HOLD.
ABORT will terminate the current running profile.
RESTART will cause the instrument to begin the profile from the beginning.

24. Press the SCROLL key and the display advances to the next profile to be configured.