West Control Solutions MRC 9000 User Manual
Page 225
![background image](/manuals/370868/225/background.png)
Edition 3
Rev G
Section 11
11-3
Step 4
Be sure that the jumpers on the Input Board for the Input being calibrated are positioned as shown in Table 11-3,
and Figure 11-1 or Table 11-3A and Figure 11-1A, depending on which circuit board is fitted.
TABLE 11-3 INPUT BOARD JUMPER POSITIONS
INPUT 1, 3, 5, 7
INPUT 2, 4, 6, 8
JU1
JU2
JU3
JU7
JU11
JU15
JU4
JU5
JU6
JU8
JU12
JU16
TC NARROW
U
L
P
R
R
P
U
R
P
R
L
P
TC WIDE
U
L
P
M
R
P
U
R
P
M
L
P
RTD
P
L
U
L
L
P
P
R
U
L
R
P
mA
U
L
P
L
R
U
U
R
P
L
L
U
25 mV
U
L
P
R
R
P
U
R
P
R
L
P
100 mV
U
L
P
M
R
P
U
R
P
M
L
P
1 VOLT
U
L
P
L
R
P
U
R
P
L
L
P
10 VOLT
U
L
D
L
R
P
U
R
D
L
L
P
INPUT 1, 3, 5, 7
INPUT 2, 4, 6, 8
JU2
JU3
JU7
JU15
JU5
JU6
JU8
JU16
TC NARROW
P
P
R
P
P
P
R
P
TC WIDE
P
P
M
P
P
P
M
P
RTD
P
U
L
P
P
U
L
P
mA
P
P
L
F
P
P
L
F
25 mV
P
P
R
P
P
P
R
P
100 mV
P
P
M
P
P
P
M
P
1 VOLT P
P
P
L
P
P
P
L
P
10 VOLT
P
D
L
P
P
D
L
P
CODE: D - DOWN, L - LEFT, M - MIDDLE, P - PARKED, R - RIGHT, U - UP, F - FITTED
FIGURE 11-1
There are up to an additional 2 jumpers per Input Board that are used for BOARD ID. Location (Board 1 is the
bottom board) determines the position of JU13 and/or JU14.
JU3
JU1
JU11
U6
JU7
+
+
-
-
1
1
TB1
TB2
JU2
JU5
JU12
JU4
JU6
JU8
JU15
JU16
U1
+
+
-
-
1
1
TB1
TB2
JU5
JU6
JU16
JU7
JU3
JU2
JU15
JU8