10.
HIGH SELECT and LOW SELECT
INPUT 1:
A
PROMPT:
DVxx INPUT A
INPUT 2:
B
PROMPT:
DVxx INPUT B
ACTUATOR:
n/a
RESET:
n/a
OUTPUT:
= HIGHER of A and B
for HIGH SELECT
= LOWER of A and B
for LOW SELECT
11.
HIGH PEAK
INPUT 1:
A
PROMPT:
DVXX INPUT
ACTUATOR:
n/a
RESET:
YES
PROMPT:
DVxx RESET ACTUATOR
OUTPUT:
= HIGHEST VALUE of A since last RESET
Whenever RESET is active, the HIGHEST VALUE will be the current value of A.
12.
LOW PEAK
INPUT 1:
A
PROMPT:
DVxx INPUT
ACTUATOR:
n/a
RESET:
YES
PROMPT:
DVXX RESET ACTUATOR
OUTPUT:
= LOWEST VALUE of A since last RESET.
Whenever RESET is active, the LOWEST VALUE will be the current value of A.
13.
TRACK AND HOLD
INPUT 1:
A
PROMPT:
DVxx INPUT
ACTUATOR:
YES
PROMPT:
DVxx TRACK ACTUATOR
RESET:
n/a
OUTPUT:
= Current value of A if the state of the Selected Actuator is true
= Last value of A when the state of the Selected Actuator changed from true to false
14.
1 of 2 SELECTOR
INPUT 1:
A
PROMPT:
DVxx INPUT A
INPUT 2:
B
PROMPT:
DVxx INPUT B
ACTUATOR:
YES
PROMPT:
DVxx SELECT B ACTUAT
RESET:
n/a
OUTPUT:
= A if the state of the Selected Actuator is false.
= B if the state of the Selected Actuator is true.
15.
CONVERT ACTUATOR
ACTUATOR:
YES
PROMPT:
DVxx ACTUATOR
RESET:
n/a
OUTPUT:
= 0.0 if the state of the Selected Actuator is false
= 1.0 if the state of the Selected Actuator is true.
16.
CONVERT F TO C
INPUT 1:
A
PROMPT:
DVxx INPUT
°
F
ACTUATOR:
n/a
RESET:
n/a
OUTPUT:
= (A-32) * 5/9