beautypg.com

West Control Solutions MRC 9000 User Manual

Page 111

background image

Edition 3

Rev G

Section 4

4-29

NOTES:

DP - Differential Pressure
PRES - Static Pressure - must be ABSOLUTE
TEMPF - Flow Temperature - must be degrees F
COMP - Compressibility Correction
C - Scaling Constant

This function converts TEMP from degrees F to degrees R in the equation.

7.

RELATIVE HUMIDITY

INPUT 1:

DBT

PROMPT:

DVxx DRY BULB TEMP

°

F

INPUT 2:

WBT

PROMPT:

DVxx WET BULB TEMP

°

F

INPUT 3:

BARO

PROMPT:

DVxx BARO. PRES "Hg

ACTUATOR:

n/a

RESET:

n/a

OUTPUT:

= RELATIVE HUMIDITY in PERCENT (0 to 100 typ)

If INPUT 3 is "NOT USED", then BARO=29.921

NOTES:

DBT - DRY BULB TEMPERATURE - must be in degrees F
WBT - WET BULB TEMPERATURE - must be in degrees F
BARO - ATMOSPHERIC PRESSURE - must be in "Hg (inches of Mercury)

8.

Fo VALUE - STERILIZATION CONSTANT Fo

INPUT 1:

INTEMP

PROMPT:

DVxx INPUT TEMP

INPUT 2:

STEMP

PROMPT:

DVxx STERILIZE TEMP

INPUT 3:

Z

PROMPT:

DVxx "Z" VALUE

ACTUATOR:

n/a

RESET:

YES

PROMPT:

DVxx RESET ACTUATOR

OUTPUT:

= DV + (10**A)/60

where: A=(INTEMP - STEMP) / Z

DV is the previous result

NOTES:

INTEMP - Input Temperature
STEMP - Sterilizing Temperature
Z - "Z" Value

The TEMPERATURE can be degrees F or C, but the "Z" value must take this into account.
Whenever RESET is active, DV will be set to zero.
The units of the resultant DV is MINUTES
This function is calculated once a second.

9.

ZRO2 - ZIRCONIA OXYGEN SENSOR

INPUT 1:

PP

PROMPT:

DVxx PARTIAL PRES

INPUT 2:

EMF

PROMPT:

DVxx PROBE EMF mV

INPUT 3:

TEMP

PROMPT:

DVxx PROBE TEMP

°

C

ACTUATOR:

n//a

RESET:

n/a

OUTPUT:

= PP/(10**B)

where: B=EMF/(0.0496* (TEMP+273.18))

NOTES:

PP - Partial Pressure - must be in Percent
EMF - Probe EMF - must be Millivolts
TEMP - Probe Temperature - must be degrees C

This function coverts TEMP from degrees C to degrees K in the equation