West Control Solutions MRC 9000 User Manual
Page 16
Section 1
1-10
Edition 3
Rev G
OTHER INPUT SPECIFICATIONS
Processing
Square root and exponential functions for linear inputs
Value Cutoff
None, at value, to zero below value, to zero near zero
Sensor Fault Detection
Sensor break on all TCs, RTDs, 1 volt, 1 to 5 volt, 4-20mA, and millivolt inputs
Sensor high and low on all inputs, 5% above or below range
Sensor Break
Upscale or downscale
Transmitter Power Supplies
Up to four isolated 25mA @ 24VDC supplies available
RECORDING
Pen Type
Disposable 4 pen fiber tip marker assembly
Pen Colors
Red, green, blue, and black
Chart Size
10", 11", 12" (12" are 11.875" actual size)
Chart Drive
DC stepper motor
Chart Rotation
6 to 9999 hours per revolution
Recorded Values
Any of over 20 values can be trended/recorded
Recording Methods
Drag pen simulation, instantaneous value, connect the values, average value,
connect the averages
Action on New Chart
Print scales, print range list, begin normal recording
Chart Messages
Twelve
RECORDING PERFORMANCE
Chart Recording Accuracy
0.3% of chart span reference accuracy
Chart Rotation Accuracy
±
0.2 minutes for a 24 hour rotation, assuming all backlash removed
OPERATOR INTERFACE
Display
Two line, 40 character vacuum fluorescent display with .21 inch (5 mm)
high characters
Status Indicators
Eight user configurable, red LED status indicators
Keypad
Fifteen keys for programming and unit operation
Display Formats
Three, refer to manual
Display Modes
Automatic or manual sequencing
Operator Messages
Twelve
Operator Inputs
Twelve
ALARMS
Number
Up to four alarms for each of four process variables
Type
Process high or low, rate rising or falling
Hysteresis
Fully adjustable
ON/OFF OUTPUTS
On/Off Output Actuators
Any of over 100 digital values/states can be used to actuate on/off outputs
(e.g. alarms, time/dates, timers, etc.)
Relays
SPDT, contacts rated 5 amps resistive at 115 VAC,
2.5 amps resistive at 230 VAC - 1/8 HP at 230 VAC (single phase), 250 VA at 115/230 VAC.
Solid State Relay Driver
Open collector output, can provide 40mA at 3 VDC or 20mA at 4VDC
Short circuit current is limited to 100 mA
Pulsed Outputs
50ms pulse when used with totalizer pulsed outputs