West Control Solutions Pro-16 User Manual
Page 83
Technical Data
9499-040-093811 / 59537-1
Page 83 of 88
Pro-16
Table 1 Thermocouples measuring ranges
Thermocouple type
Measuring range
Accuracy
Resolution (Ø)
L
Fe-CuNi (DIN)
-100...900°C
-148...1652°F
ß 2K
0,1 K
J
Fe-CuNi
-100...1200°C
-148...2192°F
ß 2K
0,1 K
K
NiCr-Ni
-100...1350°C
-148...2462°F
ß 2K
0,2 K
N
Nicrosil/Nisil
-100...1300°C
-148...2372°F
ß 2K
0,2 K
S
PtRh-Pt 10%
0...1760°C
32...3200°F
ß 2K
0,2 K
R
PtRh-Pt 13%
0...1760°C
32...3200°F
ß 2K
0,2 K
T
Cu-CuNi
-200...400°C
-328...752°F
ß 2K
0,05 K
C
W5%Re-W26%Re
0...2315°C
32...4199°F
ß 2K
0,4 K
D
W3%Re-W25%Re
0...2315°C
32...4199°F
ß 2K
0,4 K
E
NiCr-CuNi
-100...1000°C
-148...1832°F
ß 2K
0,1 K
B *
PtRh-Pt6%
0(100)...1820°C
32(212)...3308°F
ß 2K
0,3 K
* Specifications valid for 100°C
Table 2 Resistance transducer measuring ranges
Type
Measuring current
Measuring range
Accuracy
Resolution (Ø)
Pt100
0,2mA
-200...100°C -140...212°F
ß 1K
0,1K
Pt100 -200...850°C
-140...1562°F
ß 1K
0,1K
Pt1000 -200...200°C
-140...392°F
ß 2K
0,1K
KTY 11-6 *
-50...150°C
-58...302°F
ß 2K
0,05K
Special 0...4500
ß 0,1 %
0,01 %
Special 0...450
Potentiometer 0...160
Potentiometer 0...450
Potentiometer 0...1600
* Or special
Table 3 Current and voltage measuring ranges
Measuring range
Input resistance
Accuracy
Resolution (Ø)
0-10 Volt
~ 110 k
ß 0,1 %
0,6 mV
0-20 mA
49
(voltage requirement ß 2,5 V)
ß 0,1 %
1,5
A