beautypg.com

West Control Solutions Pro-16 User Manual

Page 69

background image

Programmer

9499-040-93811 / 59537-1

Page 69 of 88

Pro-16

8.4.2

Programmer set-up:

The instrument is factory-configured as a program controller. The following settings must
be checked:

Set-point function
For using the controller as a programmer, select parameter

SP.Fn

= 1 / 9 in the

ConF

menu (

r page 27).

Time base
The time base can be set to hours:minutes or minutes:seconds in the

ConF

menu;

parameter

t.bAS

(

r page 29).

Digital signals
For assigning a control output, program end or the operator call as a digital signal to
one of the outputs, set parameter

P.End

,

PrG1

PrG4

or

CALL

to 1 for the

relevant output

OUT.1

...

OUT.6

in menu ConF (

r page 31 ff).

Programmer operation
The programmer can be started, stopped and reset via one of the digital inputs
di1..4. Which input should be used for each function is determined by selecting
parameters

P.run

and

P.oFF

= 2 - 5 or 7 -9 in the

ConF

menu

Logi

accordingly (

r page 35).


Further settings, which affect the programmer display layout and operation are only
possible using the BlueControl software (see picture below)

Cutout from the BlueControl

®

Configuration “

othr”

Programmer parameter setting
16 programmers with 16 segments each are available to the user. The relevant parameters
must be determined in menu ProG . (

r page 66).

The procedure for editing a program is shown below.

Select the program you want to edit by means of keys

ÌÈ

and confirm it with

Щ

.