Level – West Control Solutions Pro-16 User Manual
Page 60
Calibration
level
9499-040-93811 / 59537-1
Page 60 of 88
Pro-16
InH.1:
The input value of the upper scaling point is displayed. The operator must
0.0
adjust the upper input value by means of the process value simulator and
confirm the input value by pressing key
Ù
.
OuH.1:
The display value of the upper scaling point is displayed. Before
0.0
calibration
OuH.1 is equal to InH.1.The operator can correct the
upper display value by pressing keys
ÌÈ
Subsequently, he confirms the
display value by pressing key
Ù
.
2-point correction (
ConF/ InP.1 / Corr = 2 ):
is possible off-line with process value simulator
g
The parameters (
OuL.1, OuH.1) altered at CAL level can be reset by
decreasing them below the lowest adjustment value (
OFF) using the
decrement key
М
.
- 2300 (18 pages)
- 3300 (2 pages)
- 4100+ (177 pages)
- N4100 (79 pages)
- N4400 (38 pages)
- N6500 (2 pages)
- N6600 (114 pages)
- N8800 (88 pages)
- N8840 (90 pages)
- 9300 (2 pages)
- 9500 (24 pages)
- D280-1 (49 pages)
- KS 40-1 (60 pages)
- KS 40-1 Burner (40 pages)
- KS 45 (76 pages)
- KS 50-1 (72 pages)
- KS 90-1 (84 pages)
- KS 90-1 Programmer manual (84 pages)
- KS 94 (44 pages)
- ProVU 4 (184 pages)
- Pro-8 (72 pages)
- Pro-4 (84 pages)
- ProEC44 (274 pages)
- CI 45 (60 pages)
- SG 45 (56 pages)
- DataVU 5 (136 pages)
- DataVU 7 (208 pages)
- MRC 5000 Controller Manual (32 pages)
- MRC 5000 Recorder Manual (32 pages)
- MRC 7000 Controller Manual (74 pages)
- MRC 7000 Recorder Manual (64 pages)
- MRC 7000 Profiler Manual (84 pages)
- MRC 8000 (76 pages)
- MRC 9000 (318 pages)
- N8080 (for 1xxx) (40 pages)
- N8080 (for 2xxx) (39 pages)
- TB 40-1 Temperature Limiter (32 pages)
- TB 40-1 Temperature Monitor (32 pages)
- TB 45 Temperature Limiter (51 pages)
- TB 45 Temperature Monitor (52 pages)
- CALogix (44 pages)
- KS 800 Operating Instructions (36 pages)
- KS 800 ISO1745 Interface Manual (34 pages)
- KS 800 Profibus Interface Manual (52 pages)