Calibration

level

9499-040-93811 / 59537-1

Page 60 of 88

Pro-16

InH.1:

The input value of the upper scaling point is displayed. The operator must

0.0

adjust the upper input value by means of the process value simulator and

confirm the input value by pressing key

Ù

.


OuH.1:

The display value of the upper scaling point is displayed. Before

0.0

calibration

OuH.1 is equal to InH.1.The operator can correct the

upper display value by pressing keys

ÌÈ

Subsequently, he confirms the

display value by pressing key

Ù

.


2-point correction (

ConF/ InP.1 / Corr = 2 ):

is possible off-line with process value simulator

g

The parameters (

OuL.1, OuH.1) altered at CAL level can be reset by

decreasing them below the lowest adjustment value (

OFF) using the

decrement key

М

.