Operation

9499-040-93811 / 59537-1

Page 20 of 88

Pro-16

3.7.7

Self-tuning start

The operator can start self-tuning at any time. For this, keys

Ù

and

È

must be pressed

simultaneously. With blinking in the second row the active adaptation is displayed
Ad:PIR. The controller outputs 0%, waits until the process is at rest and starts self-
tuning:

Ad:Stp

The self-tuning attempt is started when the following prerequisite is met:

The difference between process value

i set-point must be  10% of the set-point

range (

SP.Hi - SP.LO) (with inverse action: process value smaller than set-

point, with direct action: process value higher than set-point).

After successful self-tuning, the AdA-LED is off and the controller continues operating with
the new control parameters.

Self-tuning cancellation by the operator:

Self-tuning can always be cancelled by the operator. For this, press

Ù

and

È

key

simultaneously. The controller continues operating with the old parameters in automatic
mode in the first case and in manual mode in the second case.

Self-tuning cancellation by the controller:

An error detected during self-tuning means that the technical conditions prevent successful
self-tuning.
In this case, self-tuning was cancelled by the controller. The controller switches off its
outputs (controller output 0%), to avoid exceeding the setpoint.
The user has two possibilities to acknowledge a failed adaptation:
1.

Press keys

Ù

and

È

simultaneously:

The controller continues controlling using the old parameters in automatic mode. The
self-tuning error must be acknowledged in the error list.

2.

Press key

Ù

:

Display of error list at extended operating level. After acknowledgement of the error
message, the controller continues control in automatic mode using the old
parameters.

Cancellation causes:

r page 13: "Error status"

Acknowledgement of failed self-tuning

When pressing the

Ù

key, the controller switches over to correcting variable display

(

Y ....). After pressing the key again, the controller goes to the error list of the extended

operating level. The error message can be acknowledged by switching the message to 0
using the

Ì

- or the

È

key.

After acknowledging the error message, the controller continues operating in the automatic
mode, using the parameters valid prior to self-tuning start.

3.7.8

Examples for self-tuning attempts

(controller inverse, heating or heating/cooling)