Programmer

9499-040-93811 / 59537-1

Page 62 of 88

Pro-16

8.1.1

Programmer display

Programmer is in reset and the internal controller set-
point is effective. Segment or program number and
OFF are displayed (configurable with BlueControl:
Configuration

r Other r PDis3).

Programmer running (run LED is lit). Segment or
program number, segment type (

/

rising;

\

falling;

-

hold) and program/segment rest time or runtime

are displayed (configurable with BlueControl:
Configuration

r Other r PDis3).

Program end was reached. The set-point defined in
the last segment is effective. Segment or program
number and

End are displayed (configurable with

BlueControl: Configuration

r Other r PDis3).

Function key

è was used to switch over to the

controller. The instantaneously effective correcting
variable is displayed.

8.1.2

Segment type

Ramp-
segment
(time)

With a ramp segment (time), the set-point runs
linearly from the start value (end of previous
segment) towards the target set-point (Sp) of the
relevant segment during time Pt (segment
duration).

Ramp-
segment
(gradient)

With a ramp segment (gradient), the set-point
runs linearly from the start value (end value of
previous segment) towards the target value (Sp)
of the relevant segment. The gradient is
determined by parameter Pt.

Hold
segment

With a hold segment, the end set-point of the
previous segment is output constantly during a
defined time which is determined by parameter
Pt.

Step
segment

With a step segment, the program set-point
goes directly to the value specified in parameter
Sp. With configured control deviation alarms,
the alarm is suppressed within band monitoring.