4 configuration examples, Level – West Control Solutions Pro-16 User Manual
Page 46
Configuration
level
9499-040-93811 / 59537-1
Page 46 of 88
Pro-16
4.4 Configuration examples
4.4.1
On-Off controller / Signaller (inverse)
ConF/Cntr:
SP.Fn
= 0
set-point /cascade controller
C.Fnc
= 0
signaller with one output
C.Act
= 0
inverse output action (e.g. heating applications)
ConF/Out.1: O.Act
= 0
output action Out.1 direct
Y.1
= 1
control output Y1 active
PArA/Cntr:
HYS.L
= 0...9999
switching difference below SP
PArA/Cntr:
HYS.H
= 0...9999
switching difference above SP
PArA/SEtP:
SP.LO
= -1999...9999 lower set-point limit for Weff
SP.Hi
= -1999...9999 upper set-point limit for Weff
g
For direct signaller action, the controller action must be changed
(
ConF / Cntr / C.Act = 1 )
See also other documents in the category West Control Solutions Equipment:
- 2300 (18 pages)
- 3300 (2 pages)
- 4100+ (177 pages)
- N4100 (79 pages)
- N4400 (38 pages)
- N6500 (2 pages)
- N6600 (114 pages)
- N8800 (88 pages)
- N8840 (90 pages)
- 9300 (2 pages)
- 9500 (24 pages)
- D280-1 (49 pages)
- KS 40-1 (60 pages)
- KS 40-1 Burner (40 pages)
- KS 45 (76 pages)
- KS 50-1 (72 pages)
- KS 90-1 (84 pages)
- KS 90-1 Programmer manual (84 pages)
- KS 94 (44 pages)
- ProVU 4 (184 pages)
- Pro-8 (72 pages)
- Pro-4 (84 pages)
- ProEC44 (274 pages)
- CI 45 (60 pages)
- SG 45 (56 pages)
- DataVU 5 (136 pages)
- DataVU 7 (208 pages)
- MRC 5000 Controller Manual (32 pages)
- MRC 5000 Recorder Manual (32 pages)
- MRC 7000 Controller Manual (74 pages)
- MRC 7000 Recorder Manual (64 pages)
- MRC 7000 Profiler Manual (84 pages)
- MRC 8000 (76 pages)
- MRC 9000 (318 pages)
- N8080 (for 1xxx) (40 pages)
- N8080 (for 2xxx) (39 pages)
- TB 40-1 Temperature Limiter (32 pages)
- TB 40-1 Temperature Monitor (32 pages)
- TB 45 Temperature Limiter (51 pages)
- TB 45 Temperature Monitor (52 pages)
- CALogix (44 pages)
- KS 800 Operating Instructions (36 pages)
- KS 800 ISO1745 Interface Manual (34 pages)
- KS 800 Profibus Interface Manual (52 pages)