Page 33: Out.2 / 4 / 6

background image

Configuration

level

9499-040-93811 / 59537-1

Page 33 of 88

Pro-16

0

not active

1

active

Out.0 -1999...9999 Scaling of the analog output for 0% (0/4mA or 0/2V, only

visible when

O.TYP

=1..5)

0

Out.1 -1999...9999 Scaling of the analog output for 100% (20mA or 10V, only

visible when

O.TYP

=1..5)

100

O.Src

Signal source of the analog output OUT3 (only visible when

O.TYP

=1..5)

1

0 not

used

1

controller output y1 (continuous)

2

controller output y2 (continuous)

3 process

value

4

effective set-point Weff

5

control deviation xw (process value - set-point)

6 No

function

fOut

Forcing OUT1 (only visible with BlueControl!)

0

0 No

forcing

1

Forcing via serial interface

Out.3

Configuration parameters

Out.2

as

Out.1

except for: Default

Y.1

= 0,

Y.2

= 1

Out.5

Configuration parameters

Out.5

as

Out.1

except for default values:

All values are 0!

Out.2 / 4 / 6

Name

Value range

Description

Default

O.Act

Method of operation of output

1

0

direct / normally open

1

inverse / normally closed

Y.1
Y.2

Controller output Y1/Y2

0

0 not

active

1 active

Lim.1
Lim.2
Lim.3

Limit 1/2/3 signal

1

0 not

active

1 active

LP.AL

Interruption alarm signal (LOOP)

0

0 not

active

1 active

HC.AL

Heating current alarm signal

0