Level, Out.3, Out.5 – West Control Solutions Pro-16 User Manual
Page 33: Out.2 / 4 / 6
Configuration
level
9499-040-93811 / 59537-1
Page 33 of 88
Pro-16
0
not active
1
active
Out.0 -1999...9999 Scaling of the analog output for 0% (0/4mA or 0/2V, only
visible when
O.TYP
=1..5)
0
Out.1 -1999...9999 Scaling of the analog output for 100% (20mA or 10V, only
visible when
O.TYP
=1..5)
100
O.Src
Signal source of the analog output OUT3 (only visible when
O.TYP
=1..5)
1
0 not
used
1
controller output y1 (continuous)
2
controller output y2 (continuous)
3 process
value
4
effective set-point Weff
5
control deviation xw (process value - set-point)
6 No
function
fOut
Forcing OUT1 (only visible with BlueControl!)
0
0 No
forcing
1
Forcing via serial interface
Out.3
Configuration parameters
Out.2
as
Out.1
except for: Default
Y.1
= 0,
Y.2
= 1
Out.5
Configuration parameters
Out.5
as
Out.1
except for default values:
All values are 0!
Out.2 / 4 / 6
Name
Value range
Description
Default
O.Act
Method of operation of output
1
0
direct / normally open
1
inverse / normally closed
Y.1
Y.2
Controller output Y1/Y2
0
0 not
active
1 active
Lim.1
Lim.2
Lim.3
Limit 1/2/3 signal
1
0 not
active
1 active
LP.AL
Interruption alarm signal (LOOP)
0
0 not
active
1 active
HC.AL
Heating current alarm signal
0