Level, Prog, Inp.1 – West Control Solutions Pro-16 User Manual
Page 29
Configuration
level
9499-040-93811 / 59537-1
Page 29 of 88
Pro-16
tunE
Auto-tuning at start-up
0
0
At start-up with step function
1
At start-up with impulse function. Setting for fast controlled
systems (e.g. hot runner control)
2
Always step attempt during start-up
Strt
Start of auto-tuning
0
0
no automatic start (manual start via front interface)
1
Manual or automatic start of auto-tuning at power on or when
oscillating is detected
Adt0
Optimization of T1, T2 (only visible with BlueControl!)
0
0 Automatic
optimization
1 No
optimization
Prog
Name
Value range Description
Default
t.bAS
Time base
0
0 hours:minutes
1 minutes:seconds
InP.1
Name
Value range
Description
Default
S.tYP
Sensor type selection
1
0
thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
thermocouple type J (-100...1200°C) , Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
6
thermocouple type T (-200…400°C), Cu-NiCu
7
thermocouple type C (0...2315°C), W5%Re-W26%Re
8
thermocouple type D (0...2315°C), W3%Re-W25%Re
9
thermocouple type E (-100...1000°C), NiCr-CuNi
10
thermocouple type B (0/100...1820°C), PtRh-Pt6%
18 special
thermocouple
20
Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring
resistance + lead resistance
160
[)
21
Pt100 (-200.0 ... 850.0 °C)
22
Pt1000 (-200.0 ... 850.0 °C)