Level, Prog, Inp.1 – West Control Solutions Pro-16 User Manual

Page 29

background image

Configuration

level

9499-040-93811 / 59537-1

Page 29 of 88

Pro-16

tunE

Auto-tuning at start-up

0

0

At start-up with step function

1

At start-up with impulse function. Setting for fast controlled
systems (e.g. hot runner control)

2

Always step attempt during start-up

Strt

Start of auto-tuning

0

0

no automatic start (manual start via front interface)

1

Manual or automatic start of auto-tuning at power on or when
oscillating is detected

Adt0

Optimization of T1, T2 (only visible with BlueControl!)

0

0 Automatic

optimization

1 No

optimization

Prog

Name

Value range Description

Default

t.bAS

Time base

0

0 hours:minutes

1 minutes:seconds

InP.1

Name

Value range

Description

Default

S.tYP

Sensor type selection

1

0

thermocouple type L (-100...900°C) , Fe-CuNi DIN

1

thermocouple type J (-100...1200°C) , Fe-CuNi

2

thermocouple type K (-100...1350°C), NiCr-Ni

3

thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

thermocouple type S (0...1760°C), PtRh-Pt10%

5

thermocouple type R (0...1760°C), PtRh-Pt13%

6

thermocouple type T (-200…400°C), Cu-NiCu

7

thermocouple type C (0...2315°C), W5%Re-W26%Re

8

thermocouple type D (0...2315°C), W3%Re-W25%Re

9

thermocouple type E (-100...1000°C), NiCr-CuNi

10

thermocouple type B (0/100...1820°C), PtRh-Pt6%

18 special

thermocouple

20

Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring
resistance + lead resistance

160

[)

21

Pt100 (-200.0 ... 850.0 °C)

22

Pt1000 (-200.0 ... 850.0 °C)