Level – West Control Solutions Pro-16 User Manual
Page 47
![background image](/manuals/370842/47/background.png)
Configuration
level
9499-040-93811 / 59537-1
Page 47 of 88
Pro-16
4.4.2
2-point and continuous controller (inverse)
ConF/Cntr SP.Fn
= 0
set-point / cascade controller
C.Fnc
= 1
2-point and continuous controller (PID)
C.Act
= 0
inverse action (e.g. heating applications)
ConF/Out.1: O.Act
= 0
action Out.1 direct
Y.1
= 1
control output Y1 active
ConF/Out.3: O.tYP
= 1 / 2
Out.3 Type ( 0/4 … 20mA)
Out.0
= -1999...9999 scaling analog output 0/4mA
Out.1
= -1999...9999 scaling analog output 20mA
O.Src
= 1
controller output y1 (continuous)
PArA/Cntr: Pb1
= 1...9999
proportional band 1 (heating) in units of phys. quantity
(e.g. °C)
ti1
= 0,1...9999
integral time 1 (heating) in sec.
td1
= 0,1...9999
derivative time 1 (heating) in sec.
t1
= 0,4...9999
min. cycle time 1 (heating)
PArA/SEtP: SP.LO
= -1999...999
set-point limit low for Weff
SP.Hi
= -1999...9999 set-point limit high for Weff
g
For direct controller action, the controller action must be changed
(
ConF / Cntr / C.Act = 1 )