Setp, Inp.1, Inp.2 – West Control Solutions Pro-16 User Manual
Page 55

Parameter-Level
9499-040-93811 / 59537-1
Page 55 of 88
Pro-16
SEtP
Name
Value range
Description
Default
SP.LO
-1999...9999 Set-point limit low for Weff
0
SP.Hi
-1999...9999 Set-point limit high for Weff
900
SP.2
-1999...9999 Set-point 2
0
r.SP
OFF/0,01...9999 Set-point gradient [/min]
OFF
SP.bo
-1999...9999 Boost set-point (see page 72)
30
t.bo
0...9999
Boost time (see page 72)
10
Y.St
-120...120
Start-up correcting value (see page 71)
20
SP.St
-1999...9999 Set-point for start-up
95
t.St
0...9999
Start-up hold time (see page 71)
10
SP
-1999...9999 Set-point (only visible with BlueControl!)
0
g
SP.Lo and SP.hi should be between the limits of rnGH and rnGL
see configuration
r controller page 28
InP.1
Name
Value range
Description
Default
InL.1
-1999...9999
Input value for the lower scaling point
0
OuL.1
-1999...9999
Displayed value for the lower scaling point
0
InH.1
-1999...9999
Input value for the upper scaling point
20
OuH.1
-1999...9999
Displayed value for the lower scaling point
20
t.F1
0,1...100
Filter time constant [s]
0,5
InP.2
Name
Value range
Description
Default
InL.2
-1999...9999
Input value for the lower scaling point
0
OuL.2
-1999...9999
Displayed value for the lower scaling point
0
InH.2
-1999...9999
Input value for the upper scaling point
50
OuH.2
-1999...9999
Displayed value for the upper scaling point
50