OPERATION
6
77
OPTISONIC 7300
www.krohne.com
09/2012 - 4001102303 - MA OPTISONIC 7300 R03 en
C2. .1
mode
Off (control input switched off)
Hold all outputs (hold current values, not display and counters)
Output Y (hold current values)
All outputs to zero (current values = 0%, not display and counters)
Output Y to zero (current value = 0%)
All counters (reset all counters to "0")
Counter "Z" reset (set counter 1, 2 or 3 to "0")
Stop all counters
Stop counter "Z" (stops counter 1, 2 or 3)
Zero outp.+stop Cnt. (all outputs 0%, stop all counters, not the display)
External range Y (control input for external range of current output Y) -
also make this setting on current output Y (no check if current output Y
is available)
Error reset (all resettable errors are deleted)
C2. .2
invert signal
Select: off / on
C2. .3
information
1
st
line: serial number of the I/O circuit board
2
nd
line: software version number
3
rd
line: production date of the circuit board
C2. .4
simulation
Sequence see B 1. control input X
C3 I/O counter
C3.1
counter 1
Set function of counter
stands for 1, 2, 3
C3.2
counter 2
C3.3
counter 3
C3. .1
funct. of counter
Define counter
Select:
Sum counter (counts positive and negative values)
+counter (counts only the positive values)
-counter (counts only the negative values)
Off (counter is switched off)
C3. .2
measurement
Selection of the measurement for counter
Select: volume flow / mass flow / corr. volume flow
C3. .3
low flow cutoff
Sets output value to "0".
Range: 0.0…20%
1
st
value = switching point / 2
nd
value = hysteresis
Condition: 2
nd
value ≤ 1
st
value
C3. .4
time constant
Averages measurement
Increasing value improves stability but delays the reaction.
Range: 000.0…100.0 s
C3. .5
preset value
If this value is reached, positive or negative, a signal is generated that
can be used for a status output at which "preset counter X" has to be
set.
Preset value (max. 8 digits) x.xxxxx in selected unit, see C5.7.9 + 12
C3. .6
reset counter
Sequence see Fct. A3.2, A3.3 and A3.4