ELECTRICAL CONNECTIONS
4
39
OPTISONIC 7300
www.krohne.com
09/2012 - 4001102303 - MA OPTISONIC 7300 R03 en
Pulse/frequency output passive, basic I/Os
• U
ext
≤ 32 VDC
• f
max
in operating menu set to f
max
≤ 100 Hz:
I ≤ 100 mA
open:
I ≤ 0.05 mA at U
ext
= 32 VDC
closed:
U
0, max
= 0.2 V at I ≤ 10 mA
U
0, max
= 2 V at I ≤ 100 mA
• f
max
in the operating menu set to 100 Hz < f
max
≤ 10 kHz:
I ≤ 20 mA
open:
I ≤ 0.05 mA at U
ext
= 32 VDC
closed:
U
0, max
= 1.5 V at I ≤ 1 mA
U
0, max
= 2.5 V at I ≤ 10 mA
U
0, max
= 5.0 V at I ≤ 20 mA
• If the following maximum load resistance R
L, max
is exceeded, the load resistance R
L
must be
reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
L, max
= 47 kΩ
f ≤ 1 kHz: R
L, max
= 10 kΩ
f ≤ 10 kHz: R
L, max
= 1 kΩ
• The minimum load resistance R
L, min
is calculated as follows:
R
L, min
= (U
ext
- U
0
) / I
max
• Can also be set as status output; for the electrical connection refer to status output
connection diagram.
INFORMATION!
•
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
•
Compact and field housing versions:
Compact and field housing versions:
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
compartment.
Wall-mounted version:
Wall-mounted version:
Wall-mounted version:
Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
(insulation to DIN 46245) in the terminal compartment.
•
Any connection polarity.
Figure 4-8: Pulse/frequency output passive P
p