DESCRIPTION OF HART INTERFACE

9

113

OPTISONIC 7300

www.krohne.com

09/2012 - 4001102303 - MA OPTISONIC 7300 R03 en

9.4 Inputs/outputs and HART

®

dynamic variables and device variables

The signal converter is available with various in-/output combinations.

The connection of the terminals A…D to the HART

®

dynamic variables PV, SV, TV and QV

depends on the device version.

PV = Primary Variable; SV = Secondary Variable; TV = Third Variable; QV = Quarternary Variable

The signal converter can provide up to 14 measurement-related values. These values are
accessible as so-called HART

®

device variables and can be connected to the HART

®

dynamic

variables. The availability of these variables depends on the device versions and the settings.

Code = device variable code

Device variables

For the dynamic variables connected to the linear analogue outputs (for current and/or
frequency) are assigned by selecting the measurement for the related outputs. Only linear
device variables can be assigned in this case.

For dynamic variables not connected to linear analogue outputs both linear and totaliser device
variables can be assigned.

Signal converter version

HART

®

dynamic variable

PV

SV

TV

QV

Basic I/O, connection terminals

A

D

-

-

Modular I/O and Ex i I/O, connection terminals

C

D

A

B

HART

®

device variable

Code Type

Explanations

volume flow

20

linear

corrected volume flow

21

linear

mass flow

22

linear

molar mass

23

linear

flow speed

25

linear

velocity of sound

26

linear

signal gain

27

linear

diagnosis 1

28

linear

Function and availability depends on diagnosis 1 value

setting.

diagnosis 2

29

linear

Function and availability depends on diagnosis 2 value

setting.

diagnosis 3

30

linear

Function and availability depends on diagnosis 3 value

setting.

counter 1 (C)

6

totaliser

Valid for Basic I/O option only.

counter 1 (B)

13

totaliser

Valid for Modular I/O and Ex i I/O options only.

counter 2 (D)

14

totaliser

-

counter 3 (A)

12

totaliser

Valid for Modular I/O and Ex i I/O options only.