6

OPERATION

70

OPTISONIC 7300

www.krohne.com

09/2012 - 4001102303 - MA OPTISONIC 7300 R03 en

C1.13

temperature

Only available if ‘fixed’ is selected in C1.12

Process temperature

Select value

Range: -40.00…+800.0 °C

C1.14

pressure

Only available if ‘fixed’ is selected in C1.12

Process pressure

Select value

Range: 1.00...250.00 bara

C1.15

density

Before entering first save the setting in C1.11 and leave the menu.

Select value for density at reference conditions as selected in C1.11

C1.16

diagnosis value

C1.16.1

diagnostics 1

Select: none / SNR 1 / gain 1 / velocity of sound 1

C1.16.2

diagnostics 2

Select: none / SNR 2 / gain 2 / velocity of sound 2

C1.16.3

diagnostics 3

Select: none / SNR 3 / gain 3 / velocity of sound 3

C2 inputs/outputs (I/Os)

C2.1

hardware

Assignment of connection terminals dependent on signal converter

version: active / passive / NAMUR

C2.1.1

terminal A

Select: off (switched off) / current output / frequency output / pulse

output / status output / limit switch / control input / current input

(for pressure)

C2.1.2

terminal B

Select: off (switched off) / current output / frequency output / pulse

output / status output / limit switch / control input / current input

(for temperature)

C2.1.3

terminal C

Select: off (switched off) / current output / status output / limit switch

C2.1.4

terminal D

Select: off (switched off) / frequency output / pulse output /

status output / limit switch

current input X

C2.…

current input X

Only available if terminal A and B are current input.

X stands for one of the connection terminals A or B.

…

stands for A or B.

C2.….1

range 0%…100%

Current range for the selected measured variable, e.g. 4...20 mA,

corresponds to 0…100%.

xx.x … xx.x mA

Range: 04.0…20.0 mA

Condition: 4 mA ≤ 1

st

value ≤ 2

nd

value ≤ 20 mA

C2.….2

extended range

Exceeding the min. and max. limits.

xx.x … xx.x mA

Range: 00.5…23 mA

Condition: 0.5 mA ≤ 1

st

value ≤ 2

nd

value ≤ 23 mA

C2.….3

measurement

Terminal A: pressure

Terminal B: temperature