A1.4 list of signal characterizer block parameters, A1.4, A1-5 – Yokogawa EJX930A User Manual
Page 82
A1-5
IM 01C25T02-01E
A1.4 List of Signal Characterizer Block Parameters
Relative
Index
Parameter
Write
Mode
Valid Range
Initial
Value
View
Description / Remarks
1 2 3 4
0
BLOCK_
HEADER
Block
Tag=O/S
TAG: "SC"
Information relating to this function block, such as
block tag, DD revision, and execution time
1
ST_REV
- - - - -
2 2 2 2 The revision level of the set parameters associated
with the Signal Characterizer block
2
TAG_DESC
Null
Stores comments describing tag information.
3
STRATEGY
1
2 The strategy field can be used by the high-level
system to identify function blocks.
4
ALERT_KEY
1-255
1
1 Key information used to identify the location at which
an alert has occurred
5
MODE_BLK
4
4
Mode of the Signal Characterizer block. O/S, Man,
and Auto are supported.
6
BLOCK_ERR
2
2
Indicates the error status of the Signal Characterizer
block in bit strings.
7
OUT_1
MAN
5
5
Outputs the result of the value of IN_1 corrected
using a line-segment function.
8
OUT_2
MAN
5
5
Outputs the result of the value of IN_2 corrected
using a line-segment function. It is also possible to
approximate the result using the inverse function of
the specified line-segment function. (This is used for
backward control.)
9
X_RANGE
11
The engineering unit of variables corresponding to
the x-axis for display
10
Y_RANGE
11
The engineering unit of variables corresponding to
the y-axis for display
11
GRANT_DENY
2
The parameter used to check if various operations
have been executed.
The bits in the GRANT parameter corresponding to
various operations are set before being executed.
After the operations are complete, the DENY
parameter is checked for the setting of any bit
relating to the corresponding operation. If no bit
is set, it is evident that the operations have been
executed successfully.
12
IN_1
5
5
Input a signal to be corrected using a line-segment
function.
13
IN_2
5
5
Input a signal to be corrected using a line-segment
function.
14
SWAP_2
0:Initialized
1:No swap
2:Swap
1 Selector switch used to apply the inverse function to
line-segment approximation of IN_2 to OUT_2
15
CURVE_X
Curve input points that determine inputs and
outputs.
The "x" points of the curve are defined by an array of
1 to 21 points with a monotone increase.
16
CURVE_Y
Curve input points that determine inputs and
outputs.
The "y" points of the curve are defined by an array of
1 to 21 points.
If SWAP_2 is on, the elements of the curve must be
defined with a monotone increase or decrease.
17
UPDATE_EVT
Indicates event information if an update event
occurs.
18
BLOCK_ALM
Indicates alarm information if a block alarm occurs.