Yokogawa EJX930A User Manual
Page 59
<8. Device Information>
8-2
IM 01C25T02-01E
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x02000000
Capsule
EEPROM
Failure 2
(AL-01)
Capsule EEPROM
failed 2.
F
0x00800000
Amp Temp
Sensor
Failure (AL-
02)
Amplifier Temp
Sensor failed.
F
0x00400000
Amp
EEPROM
Failure 1
(AL-02)
Amplifier
EEPROM failed 1.
F
0x00200000
Amp
EEPROM
Failure 2
(AL-02)
Amplifier
EEPROM failed 2.
F
0x00100000
CPU Board
Failure 1
(AL-02)
CPU board failed
1.
F
0x00080000
CPU Board
Failure 2
(AL-02)
CPU board failed
2.
F
0x00040000
CPU Board
Failure 3
(AL-02)
CPU board failed
3.
F
0x00020000
CPU Board
Failure 4
(AL-02)
CPU board failed
4.
F
0x00010000
No Device ID No Device ID.
F
0x00008000
CPU Board
Failure 5
(AL-02)
CPU board failed
5.
F
Table 8.3
Contents of DEVICE_STATUS_3
(index 1047)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x80000000
Diff Pressure
outside
Range Limit
(AL-10)
Input Pressure
is outside
measurement
range limit of
capsule
S
0x40000000
Static
Pressure
outside
Range Limit
(AL-11)
Static Pressure
exceeds limit
S
0x20000000
Capsule
Temp outside
Range Limit
(AL-12)
Capsule
Temperature is out
of range
S
0x10000000
Amp Temp
outside
Range Limit
(AL-13)
Amplifier
Temperature is out
of range
S
0x00008000
No FB
Scheduled
(AL-20)
No Function Block
is scheduled.
C
Table 8.4
Contents of DEVICE_STATUS_4
(index 1048)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x80000000
AI1 Hi Hi
Alarm (AL-
30)
Hi_Hi Alarm occurs
in AI1 Function
block
—
0x40000000
AI1 Lo Lo
Alarm (AL-
30)
Lo_Lo Alarm
occurs in AI1
Function block
—
0x20000000
AI2 Hi Hi
Alarm (AL-
31)
Hi_Hi Alarm occurs
in AI2 Function
block
—
0x10000000
AI2 Lo Lo
Alarm (AL-
31)
Lo_Lo Alarm
occurs in AI2
Function block
—
0x08000000
AI3 Hi Hi
Alarm (AL-
32)
Hi_Hi Alarm occurs
in AI3 Function
block
—
0x04000000
AI3 Lo Lo
Alarm (AL-
32)
Lo_Lo Alarm
occurs in AI3
Function block
—
0x02000000
PID Hi Hi
Alarm (AL-
33)
Hi_Hi Alarm occurs
in PID Function
block
—
0x01000000
PID Lo Lo
Alarm (AL-
33)
Lo_Lo Alarm
occurs in PID
Function block
—
0x00008000
RB in O/S
Mode (AL-
40)
Resource Block is
in O/S mode
—
0x00004000
Sensor TB
in O/S Mode
(AL-41)
Sensor Transducer
Block is in O/S
mode.
C
0x00002000
LCD TB in
O/S Mode
LCD Transducer
Block is in O/S
mode.
C
0x00000800
AI1 in O/S
Mode (AL-
43)
AI1 block is in O/S
mode
C
0x00000400
AI2 in O/S
Mode (AL-
44)
AI2 block is in O/S
mode
C
0x00000200
AI3 in O/S
Mode (AL-
45)
AI3 block is in O/S
mode
C
0x00000100
AI1 Not
Scheduled
(AL-46)
AI1 block is not
scheduled
C
0x00000080
AI2 Not
Scheduled
(AL-47)
AI2 block is not
scheduled
C
0x00000040
AI3 Not
Scheduled
(AL-48)
AI3 block is not
scheduled
C