<2. Handling Cautions>

2-6

IM 01C25T02-01E

• WARNING:

WHEN AMBIENT TEMPERATURE ≥ 65°C,

USE THE HEAT-RESISTING CABLES ≥

90°C.

QUAND LA TEMPÉRATURE AMBIANTE

≥ 65°C, UTILISEZ DES CÂBLES

RÉSISTANTES Á LA CHALEUR ≥ 90°C.

• Take care not to generate mechanical

sparking when accessing to the instrument

and peripheral devices in a hazardous

location.

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation and Yokogawa Corporation of

America is prohibited and will void Canadian

Standards Explosionproof Certification.

Non-hazardous

Location

Equipment

32 V DC Max.

15 mA DC

Signal

Non-Hazardous

Locations

Hazardous Locations Division 1

Non-Hazardous

Locations

Hazardous Locations Division 2

50 cm Max.

Sealing Fitting

Conduit

Non-hazardous

Location

Equipment

32 V DC Max.

15 mA DC

Signal

Sealing Fitting

SUPPL

Y

PULSE

CHECK

ALARM

Transmitters

SUPPL

Y

PULSE

CHECK

ALARM

Transmitters

F0204.ai

b. CSA Intrinsically safe and Nonincendive

Type

The transmitters with optional code /CS15.

• Certificate: 1689689

• Applicable standard: C22.2 No.0, C22.2 No.0.4,

C22.2 No.25, C22.2 No.94, C22.2 No.157,

C22.2 No.213, C22.2 No.61010-1-04, C22.2

CAN/CSA E60079-0, CAN/CSA E60079-11,

CAN/CSA E60079-15, IEC 60529

• CSA Intrinsically Safe Approval

Class I, Division 1, Groups A, B, C, & D; Class

II, Division 1, Groups E, F & G; Class III; Ex ia

IIC T4

Ambient Temperature: –40* to 60°C (–40* to

140°F) Encl. NEMA 4X, IP66/IP67

* –15°C when /HE is specified.

• CSA Nonincendive Approval

Class I, Division 2, Groups A, B, C, & D; Class

II, Division 2, Groups F & G; Class III; Ex nL IIC

T4

Ambient Temperature: –40* to 60°C (–40* to

140°F) Encl. NEMA 4X, IP66/ IP67

* –15°C when /HE is specified.

Caution for CSA Intrinsically safe type.

(Following contents refer to “DOC. No.

ICS018)

Installation Diagram for Intrinsically safe

(Division 1 Installation)

Non-Hazardous Location

Hazardous Location

F0205.ai

Terminator

Safety Barrier

Field Instruments

Pressure

Transmitter

Field Instruments

+

+

+

Terminator

+

+

Note 1. The safety barrier must be CSA certified.
Note 2. Input voltage of the safety barrier must be

less than 250Vrms/Vdc.