Yokogawa EJX930A User Manual
Page 75
<9. Parameter Lists>
9-11
IM 01C25T02-01E
Relative
Index
Index
AI1
Index
AI2
Index
AI3 Parameter Name Factory Default
Write
Mode
Explanation
20
4020
4120
4220
UPDATE_EVT
—
—
This alert is generated by any change to the static
data.
21
4021
4121
4221
BLOCK_ALM
—
—
The block alarm is used for all configuration,
hardware, connection failure or system problems
in the block. The cause of the alert is entered in
the subcode field. The first alert to become active
will set the Active status in the Status attribute. As
soon as the Unreported status is cleared by the
alert reporting task, another block alert may be
reported without clearing the Active status, if the
subcode has changed.
22
4022
4122
4222
ALARM_SUM
Enable
—
The current alert status, unacknowledged states,
unreported states, and disabled states of the
alarms associated with the function block.
23
4023
4123
4223
ACK_OPTION
0xFFFF
AUTO Selection of whether alarms associated with the
block will be automatically acknowledged.
24
4024
4124
4224
ALARM_HYS
0.5%
AUTO Amount the PV must return within the alarm
limits before the alarm condition clears. Alarm
Hysteresis is expressed as a percent of the PV
span.
25
4025
4125
4225
HI_HI_PRI
0
AUTO Priority of the high high alarm.
26
4026
4126
4226
HI_HI_LIM
+INF
AUTO The setting for high high alarm in engineering
units.
27
4027
4127
4227
HI_PRI
0
AUTO Priority of the high alarm.
28
4028
4128
4228
HI_LIM
+INF
AUTO The setting for high alarm in engineering units.
29
4029
4129
4229
LO_PRI
0
AUTO Priority of the low alarm.
30
4030
4130
4230
LO_LIM
-INF
AUTO The setting for the low alarm in engineering units.
31
4031
4131
4231
LO_LO_PRI
0
AUTO Priority of the low low alarm.
32
4032
4132
4232
LO_LO_LIM
-INF
AUTO The setting of the low low alarm in engineering
units.
33
4033
4133
4233
HI_HI_ALM
—
—
The status for high high alarm and its associated
time stamp.
34
4034
4134
4234
HI_ALM
—
—
The status for high alarm and its associated time
stamp.
35
4035
4135
4235
LO_ALM
—
—
The status of the low alarm and its associated
time stamp.
36
4036
4136
4236
LO_LO_ALM
—
—
The status of the low low alarm and its associated
time stamp.
37
4037
4137
4237
OUT_D_SEL
0
—
Selection of alarm to output it from OUT_D
38
4038
4138
4238
OUT_D
—
Value=
MAN
A discrete value and status that shows HI_HI, HI,
LO_LO, LO state.