beautypg.com

Yokogawa EJX930A User Manual

Page 75

background image

<9. Parameter Lists>

9-11

IM 01C25T02-01E

Relative

Index

Index

AI1

Index

AI2

Index

AI3 Parameter Name Factory Default

Write

Mode

Explanation

20

4020

4120

4220

UPDATE_EVT

This alert is generated by any change to the static

data.

21

4021

4121

4221

BLOCK_ALM

The block alarm is used for all configuration,

hardware, connection failure or system problems

in the block. The cause of the alert is entered in

the subcode field. The first alert to become active

will set the Active status in the Status attribute. As

soon as the Unreported status is cleared by the

alert reporting task, another block alert may be

reported without clearing the Active status, if the

subcode has changed.

22

4022

4122

4222

ALARM_SUM

Enable

The current alert status, unacknowledged states,

unreported states, and disabled states of the

alarms associated with the function block.

23

4023

4123

4223

ACK_OPTION

0xFFFF

AUTO Selection of whether alarms associated with the

block will be automatically acknowledged.

24

4024

4124

4224

ALARM_HYS

0.5%

AUTO Amount the PV must return within the alarm

limits before the alarm condition clears. Alarm

Hysteresis is expressed as a percent of the PV

span.

25

4025

4125

4225

HI_HI_PRI

0

AUTO Priority of the high high alarm.

26

4026

4126

4226

HI_HI_LIM

+INF

AUTO The setting for high high alarm in engineering

units.

27

4027

4127

4227

HI_PRI

0

AUTO Priority of the high alarm.

28

4028

4128

4228

HI_LIM

+INF

AUTO The setting for high alarm in engineering units.

29

4029

4129

4229

LO_PRI

0

AUTO Priority of the low alarm.

30

4030

4130

4230

LO_LIM

-INF

AUTO The setting for the low alarm in engineering units.

31

4031

4131

4231

LO_LO_PRI

0

AUTO Priority of the low low alarm.

32

4032

4132

4232

LO_LO_LIM

-INF

AUTO The setting of the low low alarm in engineering

units.

33

4033

4133

4233

HI_HI_ALM

The status for high high alarm and its associated

time stamp.

34

4034

4134

4234

HI_ALM

The status for high alarm and its associated time

stamp.

35

4035

4135

4235

LO_ALM

The status of the low alarm and its associated

time stamp.

36

4036

4136

4236

LO_LO_ALM

The status of the low low alarm and its associated

time stamp.

37

4037

4137

4237

OUT_D_SEL

0

Selection of alarm to output it from OUT_D

38

4038

4138

4238

OUT_D

Value=

MAN

A discrete value and status that shows HI_HI, HI,

LO_LO, LO state.