Yokogawa EJX930A User Manual
Page 70
<9. Parameter Lists>
9-6
IM 01C25T02-01E
Relative
Index Index
Parameter Name
Factory Default Write
Mode
Explanation
18
2018
CAL_MIN_SPAN
Minimum span of
capsule
—
The minimum calibration span value allowed.
19
2019
CAL_UNIT
kPa
—
The engineering unit for the calibrated values.
20
2020
SENSOR_TYPE
Silicon resonant
—
The type of sensor.
21
2021
SENSOR_ RANGE
Range of capsule —
The High and Low range limit values, engineering units code
and the number of digits to the right of the decimal point for the
sensor.
22
2022
SENSOR_SN
Serial No.
—
Serial number.
23
2023
SENSOR_CAL_
METHOD
103: factory
trim standard
calibration
O/S
The method of the last sensor calibration.
100=volumetric
101=static weight
102=dynamic weight
103=factory trim standard calibration
104=user trim standard calibration
105=factory trim special calibration
106=user trim special calibration
255=Other
24
2024
SENSOR_CAL_LOC —
O/S
Set/indicate the location of the last sensor calibration.
25
2025
SENSOR_CAL_DATE —
O/S
Set/indicate the date of the last sensor calibration.
26
2026
SENSOR_CAL_WHO —
O/S
Set/indicate the name of the person responsible for the last
sensor calibration.
27
2027
SENSOR_
ISOLATOR_MTL
Unkown
—
Defines the construction material of the isolating diaphragms.
28
2028
SENSOR_FILL_
FLUID
Unkown
—
Defines the type of fluid used in the sensor.
29
2029
SECONDARY_VALUE
—
Static pressure (high pressure side) value and status
30
2030
SECONDARY_
VALUE_UNIT
1133 (KPa)
—
The engineering unit of static pressure (high pressure side).
This unit is linked to XD_SCALE.unit of AI blocks
31
2031
CAL_DEVIATION_HI 0
O/S
Deviation value for span adjustment.
32
2032
CAL_DEVIATION_LO 0
O/S
Deviation value for zero adjustment.
33
2033
EXTERNAL_ZERO_
TRIM
0
O/S
Permission of external zero-adjustment
34
2034
PRIMARY_VALUE_
FTIME
2
O/S
Damping time constant for primary value
35
2035
TERTIARY_VALUE
—
Value and status of static pressure at low side
36
2036
SP_VALUE_TYPE
109 (absolute
pressure)
O/S
Select the type of measurement for static pressure, absolute
or gauge
37
2037
SP_VALUE_RANGE Range of capsule —
High and low range limit values, engineering units, and decimal
point place for static pressure.
38
2038
CAL_SP_ POINT_HI 16
O/S
The highest calibrated value for static pressure
39
2039
CAL_SP_ POINT_LO 0
O/S
The Lowest calibrated value for static pressure
40
2040
CAL_SP_MIN_ SPAN 1.0
—
The minimum calibration span allowed for static pressure
41
2041
CAL_SP_UNIT
1133 (KPa)
—
The calibrated engineering unit for static pressure. This unit is
linked to XD_SCALE.unit of AI blocks
42
2042
CAL_SP_
DEVIATION_HI
0
O/S
Deviation value for span adjustment of static pressure
43
2043
CAL_SP_
DEVIATION_LO
0
O/S
Deviation value for zero adjustment of static pressure
44
2044
SP_VALUE_FTIME
2
O/S
Damping time constant for static pressure
45
2045
ATM_PRESS
101.325
O/S
Atmosphere pressure value used to obtain gauge pressure
value from absolute pressure.
46
2046
CLEAR_CAL
0
O/S
Reset zero and span adjustment to factory calibrated values for
pressure, static pressure, and or all.
47
2047
CAP_TEMP_VAL
—
Measured capsule temperature value and status.
48
2048
CAP_TEMP_RANGE -50.0 to 130.0°C —
High and low range limit values, engineering units, decimal
point place for capsule temperature.
49
2049
AMP_TEMP_VAL
—
Measured Amplifier temperature value and status.
50
2050
AMP_TEMP_ RANGE -50.0 to 95.0°C
—
High and low range limit values, engineering units, decimal
point place for Amplifier temperature.
51
2051
MODEL
Model code
—
The model code.
52
2052
SPECIAL_ ORDER_
ID
Special order
number
—
Identification number of special order.
53
2053
MANUFAC_DATE
0
O/S
Date of production