IM 01C25T02-01E
A6.5 LM Parameters
A6.5.1 LM Parameter List
The tables below show LM parameters.
Meanings of Access column entries: RW = read/write possible; R = read only
Index
(SM)
Parameter Name
Sub-parameter Name
(Sub Index)
Default Factory
Setting
Access
Remarks
375 PLME_BASIC_
CHARACTERISTICS
0
R
1 ChannelStatisticsSupported
0x00
2 MediumAndDataRatesSupported
0x4900000000000000
3 IecVersion
1 (0x1)
4 NumOfChannels
1 (0x1)
5 PowerMode
0 (0x0)
376 CHANNEL_STATES 0
R
1 channel-1
0 (0x0)
2 channel-2
128 (0x80)
3 channel-3
128 (0x80)
4 channel-4
128 (0x80)
5 channel-5
128 (0x80)
6 channel-6
128 (0x80)
7 channel-7
128 (0x80)
8 channel-8
128 (0x80)
377 PLME_BASIC_INFO 0
R
1 InterfaceMode
0 (0x0)
2 LoopBackMode
0 (0x0)
3 XmitEnabled
1 (0x1)
4 RcvEnabled
1 (0x1)
5 PreferredReceiveChannel
1 (0x1)
6 MediaTypeSelected
73 (0x49)
7 ReceiveSelect
1 (0x1)
378 DLME_LINK_MASTER_CAPABILITIES_VARIABLE
0x04
RW
379 DLME_LINK_
MASTER_INFO_
RECORD
0
RW
1 MaxSchedulingOverhead
0
2 DefMinTokenDelegTime
100
3 DefTokenHoldTime
300
4 TargetTokenRotTime
4096
5 LinkMaintTokHoldTime
400
6 TimeDistributionPeriod
5000
7 MaximumInactivityToClaimLasDelay
2
8 LasDatabaseStatusSpduDistributionPeriod 6000
380 PRIMARY_LINK_MASTER_FLAG_VARIABLE
0
RW
LAS: True = 0xFF;
non-LAS: False = 0x00
381 LIVE_LIST_STATUS_ARRAY_VARIABLE
0
R
382 MAX_TOKEN_
HOLD_TIME_
ARRAY
0
RW
1 Element1
0x0000(x16),
0x012C(x16)
2 Element2
0x012C(x5),
0x0000(x27)
3 Element3
0x0000(x32)
4 Element4
0x0000(x32)
5 Element5
0x0000(x32)
6 Element6
0x0000(x32)
7 Element7
0x0000(x31),
0x012C(x1)
8 Element8
0x012C(x32)
383 BOOT_OPERAT_FUNCTIONAL_CLASS
Specified at the time
of order
RW
0x01 (basic device);