Yokogawa EJX930A User Manual
Page 74
<9. Parameter Lists>
9-10
IM 01C25T02-01E
Relative
Index
Index
AI1
Index
AI2
Index
AI3 Parameter Name Factory Default
Write
Mode
Explanation
3
4003
4103
4203
STRATEGY
1
AUTO The strategy field can be used to identify grouping
of blocks. This data is not checked or processed
by the block.
4
4004
4104
4204
ALERT_KEY
1
AUTO The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
5
4005
4105
4205
MODE_BLK
AUTO
AUTO The actual, target, permitted, and normal modes
of the block.
6
4006
4106
4206
BLOCK_ERR
—
—
This parameter reflects the error status
associated with the hardware or software
components associated with a block. It is a bit
string, so that multiple errors may be shown.
7
4007
4107
4207
PV
—
—
Either the primary analog value for use in
executing the function, or a process value
associated with it. May also be calculated from
the READBACK value of an AO block.
8
4008
4108
4208
OUT
—
Value =
MAN
The primary analog value calculated as a result of
executing the function.
9
4009
4109
4209
SIMULATE
Disable
AUTO Allows the transducer analog input or output to
the block to be manually supplied when simulate
is enabled. When simulation is disabled, the
simulate value and status track the actual value
and status.
10
4010
4110
4210
XD_SCALE
Specified at the
time of order
O/S
The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point used with the value obtained from
the transducer for a specified channel.
11
4011
4111
4211
OUT_ SCALE
Specified at the
time of order
O/S
The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point to be used in displaying the OUT
parameter and parameters which have the same
scaling as OUT.
12
4012
4112
4212
GRANT_DENY
0
AUTO Options for controlling access of host computers
and local control panels to operating, tuning and
alarm parameters of the block.
13
4013
4113
4213
IO_OPTS
0
O/S
Options which the user may select to alter input
and output block processing
14
4014
4114
4214
STATUS_OPTS
0
O/S
Options which the user may select in the block
processing of status
15
4015
4115
4215
CHANNEL
AI1: 1
AI2: 2
AI3: 4
O/S
The number of the logical hardware channel that
is connected to this I/O block. This information
defines the transducer to be used going to or from
the physical world.
1:PV
2:SV
3:TV
4:CAP_TEMP_VAL
5:AMP_TEMP_VAL
6:FLG_TEMP_VAL
16
4016
4116
4216
L_TYPE
Specified at the
time of order
MAN
Determines if the values passed by the
transducer block to the AI block may be used
directly (Direct) or if the value is in different units
and must be converted linearly (Indirect), or with
square root (Ind Sqr Root), using the input range
defined by the transducer and the associated
output range.
17
4017
4117
4217
LOW_CUT
Linear: 0%
Square root: 10%
of OUT_SCALE
AUTO Limit used in square root processing. A value of
zero percent of scale is used in block processing
if the transducer value falls below this limit. This
feature may be used to eliminate noise near zero
for a flow sensor. The setting is in an engineering
unit of OUT_SCALE.
18
4018
4118
4218
PV_FTIME
0 (s)
AUTO Time constant of a single exponential filter for the
PV, in seconds.
19
4019
4119
4219
FIELD_VAL
—
—
Raw value of the field device in percent of thePV
range, with a status reflecting the Transducer
condition, before signal characterization (L_
TYPE) or filtering (PV_FTIME).