Page 118
A4-7
IM 01C25T02-01E
Relative
Index
Parameter
Write
Mode
Valid
Range
Initial
Value
View
Description / Remarks
1 2 3 4
21
BIAS_IN_1
0
4 IN_1 bias
22
GAIN_IN_1
0
4 IN_1 gain
23
BIAS_IN_2
0
4 IN_2 bias
24
GAIN_IN_2
0
4 IN_2 gain
25
BIAS_IN_3
0
4 IN_3 bias
26
GAIN_IN_3
0
4 IN_3 gain
27
COMP_HI_
LIM
+INF
4 High limit of compensation factor f.
28
COMP_LO_
LIM
-INF
4 Low limit of compensation factor f.
29
ARITH_
TYPE
1 to 10
0x01
1 Computation algorithm identification no.
Value
Selection Name
Description
1
Flow compensation, linear
Flow compensation (linear)
2
Flow compensation, square
root
Flow compensation (square
root)
3
Flow compensation,
approximate
Flow compensation
(approximate expression)
4
BTU flow (*)
Quantity of heat calculation
5
Traditional Multiply Divide
Multiplication and division
6
Average
Average calculation
7
Traditional summer
Summation
8
Fourth order Polynomial,
Type 1
4th-order (auxiliary input)
polynomial computation
9
HTG level compensation (*) HTG-level compensation
10
Fourth order Polynomial,
Type 2
4th-order (main input)
polynomial computation
* BTU stands for British thermal unit.
HTG stands for
hydrostatic tank gauging.
30
BAL_TIME
More
than 0
0
4 Time taken to return to the set value.
31
BIAS
0
4 Bias value used to calculate the output.
32
GAIN
1
4 Gain value used to calculate the output.
33
OUT_HI_
LIM
+INF
4 Maximum output value.
34
OUT_LO_
LIM
-INF
4 Minimum output value.
35
UPDATE_
EVT
Indicates event information if an update event (setting change)
occurs.
36
BLOCK_
ALM
Indicates alarm information if a block alarm occurs.