A8-18 – Yokogawa EJX930A User Manual
Page 162
A8-18
IM 01C25T02-01E
Checklist (2/5)
No.
Items
Parameters
Result
Example
8 Alarm status
• Check the alarm status shown in
DIAG_ERR.
• Check that the alarm status of
“Outside Diagnosis Range” is not
shown in DIAG_ERR.
DIAG_ERR (Index: 2069)
A Blocking
Large Fluctuation of Low Side
Large Fluctuation of High Side
Low Side Blocking
High Side Blocking
B Blocking
Invalid Ref BlkF
Invalid Ref fSPh
Invalid Ref fSPl
Invalid Ref fDP
Outside Diagnosis Range
Reflect Blockage to PV/SV/TV Status
9 ILBD parameters
• Record the values of parameters for
ILBD operation.
• Check the status of parameters for
ILBD operation.
*: Record the value after checked
that the status of each parameter is
“GOOD”.
DIAG_PERIOD (Index: 2067)
180
DIAG_LIM (Index: 2077)
DIAG_LIM [1]
3.000000
DIAG_LIM [2]
0.300000
DIAG_LIM [3]
5.000000
DIAG_LIM [4]
0.500000
DIAG_LIM [5]
5.000000
DIAG_LIM [6]
0.500000
DIAG_LIM [7]
0.600000
DIAG_LIM [8]
-0.600000
DIAG_LIM [9]
1.000000
DIAG_LIM [10]
0.050000
DIAG_COUNT (Index: 2078)
3
REFERENCE_TIME (Index: 2079)
16:22:55.876
01/31/2008
REFERENCE_FDP* (Index: 2080)
7.43245e-9
REFERENCE_FSPL* (Index: 2081)
7.25765e-9
REFERENCE_FSPH* (Index: 2082)
7.18374e-9
REFERENCE_DPAVG* (Index: 2084)
5.364248
VALUE_TIME (Index: 2085)
16:22:55.876
01/31/2008
VALUE_FDP (Index: 2086) *
7.48562e-9
VALUE_FSPL (Index: 2087) *
7.23277e-9
VALUE_FSPH (Index: 2088) *
7.14085e-9
VALUE_BLKF (Index: 2089) *
-0.287259
VALUE_DPAVG (Index: 2090) *
0.055957