A8.2.1 blockage detection, A8.2.1, A8-3 – Yokogawa EJX930A User Manual
Page 147
A8-3
IM 01C25T02-01E
A8.2.1 Blockage Detection
DIAG_LIM
When the parameter based on pressure fluctuation
exceeds the preset value, EJX diagnoses an
impulse line as blockage and gives an alarm. The
threshold values are set to DIAG_LIM [1] to [8] in
the SENSOR Transducer block.
TableA8.2 shows the default values at the factory
setting, which are different according to the model.
NOTE
• When ILBD is performed for the first time,
use the default value. If the pressure
fluctuation amplitude is low or a false alarm
is often generated after ILBD is performed,
change the values of DIAG_LIM according to
the procedure described in A8.2.10.
• Use Device description (DD) file for
parameter setting.
DIAG_LIM
#
Parameter
Threshold value
[1] fdpmax
Threshold to detect “A Blocking” by
using
RATIO_FDP
[2] fdpmin
Threshold to detect “B Blocking” by
using
RATIO_FDP
[3] fsplmax
Threshold to detect “Large
Fluctuation of Low Side” by using
RATIO_FSPL
[4] fsplmin
Threshold to detect “Low Side
Blocking” by using
RATIO_FSPL
[5] fsphmax
Threshold to detect “Large
Fluctuation of High Side” by using
RATIO_FSPH
[6] fsphmin
Threshold to detect “High Side
Blocking” by using
RATIO_FSPH
[7] blkfmax
Threshold to detect “High Side
Blocking” by using
VALUE_BLKF
[8] blkfmin
Threshold to detect “Low Side
Blocking” by using
VALUE_BLKF
[9] dpavgmax
Threshold to detect “Outside
Diagosis Range” by using
VALUE_
DPAVG and to detect “Invalid
Ref xx” by using
REFERENCE_
DPAVG.
[10] dpavgmin
Threshold to detect “Outside
Diagosis Range” by using
VALUE_
DPAVG and to detect “Invalid
Ref xx” by using
REFERENCE_
DPAVG.
Table A8.2 Default Values of DIAG_LIM
INDEX
Parameter
Differential pressure
transmitter
Flange
mounted
differential
pressure
transmitter
Diaphragm
sealed
differential
pressure/
pressure
transmitter
Absolute
pressure
transmitter
Gauge
pressure
transmitter
Gauge/
Absolute
pressure
transmitter
EJX110A
EJX115A
EJX120A EJX130A
EJX135A
EJX210A
EJX118A
Note 1
EJX438A
EJX310A
EJX430A
EJX440A
EJX510A
EJX530A
[1]
fDPmax
3
3
3
10000
10000
10000
10000
10000
[2]
fDPmin
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
[3]
fSPlmax
5
10000
5
10000
10000
10000
10000
10000
[4]
fSPlmin
0.5
0
0.5
0
0
0
0
0
[5]
fSPhmax
5
10000
5
10000
10000
10000
10000
10000
[6]
fSPhmin
0.5
0
0.5
0
0
0
0
0
[7]
blkfmax
0.6
10
0.6
10
10
10
10
10
[8]
blkfmin
-0.6
-10
-0.6
-10
-10
-10
-10
-10
[9]
dpavgmax
Note2
1
1
1
1
1
1
1
1
[10]
dpavgmin
Note2
0.05
0.2
0.05
-1
-1
0.05
0.05
0.05
Note 1: The default values are set for level measurement. If EJX118A is applied to the flow measurement, set the same value to
DIAG_LIM [1] to [10] as those of EJX110A.
Note 2: It indicates the threshold value for ILBD over range (refer to A8.2.5.3).