A5-3 – Yokogawa EJX930A User Manual
Page 121
A5-3
IM 01C25T02-01E
Index
Parameter
Name
Default
(factory setting)
Write
Valid Range
Description
35
RCAS_OUT
0
—
Remote setpoint sent to a computer, etc.
36
ROUT_OUT
0
—
Remote control output value.
37
TRK_SCALE
100
0
1342
1
MAN
Upper and lower scale limits used to convert the output
tracking value (TRK_VAL) to non-dimensional.
38
TRK_IN_D
0
Switch for output tracking. See Section A5.12 for
details.
39
TRK_VAL
0
Output tracking value (TRK_VAL).
When MODE_BLK.actual = LO, the value scaled from
the TRK_VAL value is set in OUT.
40
FF_VAL
0
Feedforward input value.
The FF_VAL value is scaled to a value with the same
scale as for OUT, multiplied by the FF_GAIN value, and
then added to the output of the PID computation.
41
FF_SCALE
100
0
1342
1
MAN
Scale limits used for converting the FF_VAL value to a
non-dimensional value.
42
FF_GAIN
0
MAN
Gain for FF_VAL.
43
UPDATE_EVT
—
Same as that for an AI block.
44
BLOCK_ALM
—
Same as that for an AI block.
45
ALARM_SUM
Enable
Same as that for an AI block.
46
ACK_OPTION
0xFFFF
Same as that for an AI block.
47
ALARM_HYS
0.5%
0 to 50%
Hysteresis for alarm detection and resetting to prevent
each alarm from occurring and recovering repeatedly
within a short time.
48
HI_HI_PRI
0
0 to 15
Priority order of HI_HI_ALM alarm.
49
HI_HI_LIM
+INF
PV_SCALE
Setting for HI_HI_ALM alarm.
50
HI_PRI
0
0 to 15
Priority order of HI_ALM alarm.
51
HI_LIM
+INF
PV_SCALE
Setting for HI_ALM alarm.
52
LO_PRI
0
0 to 15
Priority order of LO_ALM alarm.
53
LO_LIM
-INF
PV_SCALE
Setting for LO_ALM alarm.
54
LO_LO_PRI
0
0 to 15
Priority order of LO_LO_ALM alarm.
55
LO_LO_LIM
-INF
PV_SCALE
Setting for LO_LO_ALM alarm.
56
DV_HI_PRI
0
0 to 15
Priority order of DV_HI_ALM alarm.
57
DV_HI_LIM
+INF
Setting for DV_HI_ALM alarm.
58
DV_LO_PRI
0
0 to 15
Priority order of DV_LO_ALM alarm.
59
DV_LO_LIM
-INF
Setting for DV_LO_ALM alarm.
60
HI_HI_ALM
—
—
Alarm that is generated when the PV value has
exceeded the HI_HI_LIM value and whose priority
order* is defined in HI_HI_PRI.
* Priority order: Only one alarm is generated at a time.
When two or more alarms occur at the same
time, the alarm having the highest priority order is
generated.
When the PV value has decreased below [HI_HI_
LIM - ALM_HYS], HI_HI_ALM is reset.
61
HI_ALM
—
—
As above
62
LO_ALM
—
—
As above
Reset when the PV value has increased above
[LO_LIM + ALM_HYS].
63
LO_LO_ALM
—
—
As above
64
DV_HI_ALM
—
—
Alarm that is generated when the value of [PV - SP] has
exceeded the DV_HI_LIM value. Other features are the
same as HI_HI_ALM.
65
DV_LO_ALM
—
—
Alarm that is generated when the value of [PV - SP] has
decreased below the DV_LO_LIM value. Other features
are the same as LO_LO_ALM.