Yokogawa EJX930A User Manual
Page 63
<8. Device Information>
8-6
IM 01C25T02-01E
Table 8.11
Action of each parameters in failure mode related Function block
ALARM
Display
Cause of Alarm
Object
block
BLOCK_ERR
OUT.STATUS
AL.30
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in AI1
Function block
AI1
—
Depends on specified High High(Lo Lo)
Priority (*1)
AL.31
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in AI2
Function block
AI2
—
Depends on specified High High(Lo Lo)
Priority (*1)
AL.32
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in AI3
Function block
AI3
—
Depends on specified High High(Lo Lo)
Priority (*1)
AL.33
HI.HI
LO.LO
Hi_Hi or Lo_Lo Alarm occurs in PID
Function block
PID
—
Depends on specified High High(Lo Lo)
Priority (*1)
AL.43
AI O/S
AI1 block is O/S mode
AI1
Out-of-Service
BAD-Out of Service
AL.44
AI O/S
AI2 block is O/S mode
AI2
AL.45
AI O/S
AI3 block is O/S mode
AI3
AL.46
NO.SCHD
AI1 block is not scheduled
AI1
HOLD
HOLD
AL.47
NO.SCHD
AI2 block is not scheduled
AI2
AL.48
NO.SCHD
AI3 block is not scheduled
AI3
AL.70
PID O/S
PID.MAN
NO.SCHD
PID block is not scheduled or is MAN,
O/S mode
PID
Depends on cause of Alarm
Depends on cause of Alarm
AL.71
SC O/S
SC MAN
NO.SCHD
SC block is not scheduled or is MAN,
O/S mode
SC
Depends on cause of Alarm
Depends on cause of Alarm
AL.72
IT O/S
IT MAN
NO.SCHD
IT block is not scheduled or is MAN,
O/S mode
IT
Depends on cause of Alarm
Depends on cause of Alarm
AL.73
IS O/S
IS MAN
NO.SCHD
IS block is not scheduled or is MAN,
O/S mode
IS
Depends on cause of Alarm
Depends on cause of Alarm
AL.74
AR O/S
AR MAN
NO.SCHD
AR block is not scheduled or is MAN,
O/S mode
AR
Depends on cause of Alarm
Depends on cause of Alarm
AL.90
AI SML
Simulation function of AI1 block is
active
AI1
Simulate Active
Specified Status
AL.91
AI SML
Simulation function of AI2 block is
active
AI2
Simulate Active
Specified Status
AL.92
AI SML
Simulation function of AI3 block is
active
AI3
Simulate Active
Specified Status
AL.93
AI MAN
AI1 block is MAN mode
AI1
—
Depends on setting condition of
STATUS_OPT Limit Status:Constant
AL.94
AI MAN
AI2 block is MAN mode
AI2
—
Depends on setting condition of
STATUS_OPT Limit Status:Constant
AL.95
AI MAN
AI3 block is MAN mode
AI3
—
Depends on setting condition of
STATUS_OPT Limit Status:Constant
(*1) Priority:
0 = the associated alert will never occur.
1 = the associated alert is not sent as a notification. If the priority is above 1, then the alert must be reported.
2 = Block alarm and update event have a fixed priority of 2.
3-7 = advisory alarms (PV.STATUS = Active Advisory Alarm)
8-15 = critical alarms (PV.STATUS = Active Critical Alarm)