Yokogawa EJX930A User Manual
Page 66
<9. Parameter Lists>
9-2
IM 01C25T02-01E
Relative
Index Index
Parameter Name
Factory Default
Write
Mode
Explanation
18
1018
FEATURE_SEL
Report
Fault state
Soft W Lock
Hard W Lock
AUTO Used to select resource block options defined in FEATURES.
bit0: Scheduled
bit1: Event driven
bit2: Manufacturer specified
19
1019
CYCLE_TYPE
Scheduled
—
Identifies the block execution methods available for this
resource.
20
1020
CYCLE_SEL
Scheduled
AUTO Used to select the block execution method for this resource.
21
1021
MIN_CYCLE_T
3200 (100 ms)
—
Time duration of the shortest cycle interval of which the
resource is capable.
22
1022
MEMORY_SIZE
0
—
Available configuration memory in the empty resource. To be
checked before attempting a download.
23
1023
NV_CYCLE_T
0
—
Interval between writing copies of nonvolatile parameters to
non-volatile memory. Zero means never.
24
1024
FREE_SPACE
0
—
Percent of memory available for further configuration. DPharp
has zero which means a preconfigured resource.
25
1025
FREE_TIME
0
—
Percent of the block processing time that is free to process
additional blocks. DPharp does not support this.
26
1026
SHED_RCAS
640000 (2 S)
AUTO Time duration at which to give up on computer writes to
function block RCas locations. Supported only with PID
function.
27
1027
SHED_ROUT
640000 (2 S)
AUTO Time duration at which to give up on computer writes to
function block ROut locations. Supported only with PID
function.
28
1028
FAULT_STATE
1
—
Condition set by loss of communication to an output block,
failure promoted to an output block or a physical contact.
When fail-safe condition is set, then output function blocks will
perform their FSAFE actions.
29
1029
SET_FSTATE
1
AUTO Allows the fail-safe condition to be manually initiated by
selecting Set.
30
1030
CLR_FSTATE
1
AUTO Writing a Clear to this parameter will clear the device fail-safe
state if the field condition, if any, has cleared.
31
1031
MAX_NOTIFY
4
—
Maximum number of unconfirmed notify messages possible.
32
1032
LIM_NOTIFY
4
AUTO Maximum number of alarm information which transmitter can
transfer at the same time. Setting of this parameter restrict
number of alarm transfer to the HOST and prevent HOST from
overflow.
33
1033
CONFIRM_TIM
64000 (20 s)
AUTO The minimum time between retries of alert reports.
34
1034
WRITE_LOCK
1(Not locked)
AUTO If set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated
1: Not Locked
2: Locked
35
1035
UPDATE_EVT
—
—
This alert is generated by any change to the static data.
36
1036
BLOCK_ALM
—
—
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute.
As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
37
1037
ALARM_SUM
Enable
—
The current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function block.
38
1038
ACK_OPTION
0xFFFF
AUTO Selection of whether alarms associated with the block will be
automatically acknowledged.
39
1039
WRITE_PRI
0
AUTO Priority of the alarm generated by clearing the write lock.
40
1040
WRITE_ALM
—
—
This alert is generated if the write lock parameter is cleared.
41
1041
ITK_VER
6
—
Version number of interoperability test by Fieldbus Foundation
applied to the transmitter.
42
1042
SOFT_REV
—
Transmitter software revision number.
43
1043
SOFT_DESC
—
Yokogawa internal use.
44
1044
SIM_ENABLE_MSG
Null
AUTO Software switch for simulation function.
45
1045
DEVICE_STATUS_1
0
—
Device status For details, refer to Table 8.1
46
1046
DEVICE_STATUS_2
0
—
Device status For details, refer to Table 8.2
47
1047
DEVICE_STATUS_3
0
—
Device status For details, refer to Table 8.3
48
1048
DEVICE_STATUS_4
reserve
—
Device status For details, refer to Table 8.4