<8. Device Information>
8-3
IM 01C25T02-01E
Table 8.5
Contents of DEVICE_STATUS_5
(index 1049)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x80000000
Diff Pressure
Span Trim
Error
(AL-50)
Trimming range
error for differential
pressure span
C
0x40000000
Diff Pressure
Zero Trim
Error
(AL-50)
Trimming range
error for differential
pressure zero
C
0x20000000
Static
Pressure
Span Trim
Error
(AL-51)
Trimming range
error for static
pressure span
C
0x10000000
Static
Pressure
Zero Trim
Error
(AL-51)
Trimming range
error for static
pressure zero
C
Table 8.6
Contents of DEVICE_STATUS_6
(index 1050)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x80000000
PID in O/S
Mode (AL-
70)
PID block is in O/S
mode
C
0x40000000
PID in MAN
Mode (AL-
70)
PID block is in MAN
mode
C
0x20000000
PID Not
Scheduled
(AL-70)
PID block is not
Scheduled
C
0x10000000
PID in
Bypass
Mode
PID Block is in
Bypass mode.
C
0x08000000
SC in O/S
Mode (AL-
71)
SC block is in O/S
mode
C
0x04000000
SC in MAN
Mode (AL-
71)
SC block is in MAN
mode
C
0x02000000
SC Not
Scheduled
(AL-71)
SC block is not
scheduled
C
0x01000000
IT in O/S
Mode (AL-
72)
IT block is in O/S
mode
C
0x00800000
IT in MAN
Mode (AL-
72)
IT block is in MAN
mode
C
0x00400000
IT Not
Scheduled
(AL-72)
IT block is not
scheduled
C
0x00100000
IS in O/S
Mode (AL-
73)
IS block is in O/S
mode
C
0x00080000
IS in MAN
Mode (AL-
73)
IS block is in MAN
mode
C
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x00040000
IS Not
Scheduled
(AL-73)
IS block is not
scheduled
C
0x00020000
AR in O/S
Mode (AL-
74)
AR block is in O/S
mode
C
0x00010000
AR in MAN
Mode (AL-
74)
AR block is in MAN
mode
C
0x00008000
AR Not
Scheduled
(AL-74)
AR block is not
scheduled
C
0x00000004
IT Total
Backup Err
(AL-78)
IT Total Backup
has failed. Last IT
Output Value (IT.
LAST.VALUE) is
not saved.
F
0x00000002
LCD Display
Outside
Range Limit
(AL-79)
Displayed value
exceeds limit
C
0x00000001
LCD Display
Config Error
(AL-79)
Specified settings
for Display do not
meet the conditions
C
Table 8.7
Contents of DEVICE_STATUS_7
(index 1051) (Applicable for option
code "DG1".)
Hexadecimal
Display
through DD
Description
NAMUR
NE-107
category
0x00004000
Flg Temp
High Alarm
(AL-87)
Flange
Temperature High
Alarm occurs.
M
0x00002000
Flg Temp
Low Alarm
(AL-87)
Flange
Temperature Low
Alarm occurs.
M
0x00001000
Outside
Diagnosis
Range (AL-
89)
Outside Diagnosis
Range.
—
0x00000800
Invalid Ref
fDP (AL-88)
VALUE_FDP
under normal
conditions is not
up to the reference
fluctuation
level required
to blockage
detection.
C
0x00000400
Invalid Ref
fSPl (AL-88)
VALUE_FSPL
under normal
conditions is not
up to the reference
fluctuation
level required
to blockage
detection.
C