Relative

Index Index

Parameter Name

Factory

Default

Write

Mode

Explanation

92

2092 RATIO_FSPL

SQRT (VALUE_FSPL/REFERENCE_FSPL).

VALUE_FSPL decreases and this parameter is used to determine

whether low-pressure-side is plugged.

93

2093 RATIO_FSPH

SQRT (VALUE_FSPH/REFERENCE_FSPH).

VALUE_FSPH decreases and this parameter is used to determine

whether high-pressure-side is plugged.

94

2094 CRATIO_FDP

RATIO_FDP is compensated by following formula and used as

treatable monitoring value when the flow change is too large or

small.

CRATIO_FDP = Sqrt (VALUE_FDP/REFERENCE_FDP)

X|REFERENCE_DPAVG / DPAVG)|

When Compensation is selected in COMP_FLG, CRATIO_FDP is

used as monitoring value.

95

2095 NRATIO_FDP

When Non-compensation is selected in COMP_FLG, NRATIO_

FDP is used as monitoring value NRATIO_FDP = Sqrt (VALUE_

FDP/REFERENCE_FDP)

96

2096 DIAG_APPLICABLE

After the reference value is obtained, the applicable blockage

detection is displayed on this parameter.