7. In-Process Operation
This chapter describes the procedure performed
when changing the operation of the function block
of the transmitter in process.
7.1 Mode Transition
When the function block mode is changed to
Out_Of_Service, the function block pauses and a
block alarm is issued.
When the function block mode is changed to
Manual, the function block suspends updating of
output values. In this case alone, it is possible to
write a value to the OUT parameter of the block
for output. Note that no parameter status can be
changed.
7.2 Generation of Alarm
7.2.1 Indication of Alarm
When the self-diagnostics function indicates that a
device is faulty, an alarm (device alarm) is issued
from the resource block. When an error (block
error) is detected in each function block or an error
in the process value (process alarm) is detected, an
alarm is issued from each block. If an LCD indicator
is installed, the error number is displayed as AL.XX.
If two or more alarms are issued, multiple error
numbers are displayed.
For details of ALARM, refer to Section 8.2.
F0701.ai
Figure 7.1
Error Identification on Indicator
7.2.2 Alarms and Events
The following alarms or events can be reported by
the transmitter if Link object and VCR static entry
are set.
Analog Alerts (Generated when a process value
exceeds threshold)
By AI Block Hi-Hi Alarm, Hi Alarm, Low Alarm,
Low-Low Alarm
Discret Alerts (Generated when an abnormal
condition is detected)
By Resource Block Block Alarm, Write Alarm
By Transducer Block Block Alarm
By AI, SC, IT, IS, AR and PID Blocks
Block Alarm
Update Alerts (Generated when an important
(restorable) parameter is updated)
By Resource Block Update Event
By Transducer Block Update Event
By AI, SC, IT, IS, AR and PID Blocks
Update Event
Field Diagnostic Alerts (Generated when an
abnormal condition in field device is detected)
By Resource Block Check Alarm, Failure
Alarm, Maintenance Alarm, and off
specification Alarm.
An alert has following structure: