10. General Specifications
10.1 Standard Specifications
For items other than those described below,
refer to each User’s Manual.
Applicable Model:
All DPharp EJX/EJA series.
Output:
Digital communication signal based on
F
OUNDATION
Fieldbus protocol.
Supply Voltage:
9 to 32 V DC for general use, flameproof type
and Type n
9 to 24 V DC for intrinsically safe type Entity
model
9 to 17.5 V DC for intrinsically safe type FISCO
model
Communication Requirements:
Supply Voltage: 9 to 32 V DC
Current Draw (Stedy state): 15 mA (max)
Current Draw (Software Download state):
24 mA (max)
Update Period:
Differential Pressure: 100 ms
Static Pressure: 100 ms
Capsule Temperature: 1 s
Amplifier Temperature: 1 s
Integral Indicator (LCD display):
5-digit Numerical Display, 6-digit Unit Display
and Bar graph. The indicator is configurable
to display one or up to four of the I/O signals
periodically.
Functional Specifications:
Functional specifications for Fieldbus
communication conform to the standard
specifications (H1) of F
OUNDATION
Fieldbus.
Function Block:
Block
name Number
Execution
time
Note
AI
3
30 mS
For differential pressure,
static pressure and
temperature
SC
1
30 mS
An Output of Signal
Characterizer block is
a non-linear function of
the respective input. The
function is determined by
a table
IT
1
30 mS
Integrator block integrates
a variable as a function of
the time or accumulates
the counts
IS
1
30 mS
Input Selector block
provides selection of up to
eight inputs and generate
an output based on the
configured action
AR
1
30 mS
Arithmetic block permits
simple use of popular
measurement math
functions
PID 1
45 mS
Works as a field PID
controller in conjunction
with other function blocks.
LM Function:
LM function is supported.
LM function is disabled when shipped.