IAI America ISWA User Manual
Page 67
59
1
1. Procedure for Motor Replacement
11.2
Setting for Home Preset Value and Home-Return Offset Value
Change the parameter of the home preset value for X-SEL and SSEL controllers and the home-return
offset value for SCON controller to adjust the position. Procedure to set the parameter is described
below.
11.2.1 For XSEL and SSEL controllers
(1) Open the position edit screen.
On the PC software, click
ĺ3RVLWLRQ1R6HOHFWĺ2.WRRSHQWKHZLQGRZVKRZQEHORZ
(2) Compare the current value and the value on the position No. that the actuator is randomly moved to
FRQ¿UPWKHDPRXQWRIGLIIHUHQFH
The current value is displayed.
Position number
Press this button to select the position edit window.
Press MV button.
Select a preferable
position.
(1)
(2)