0 alpha mib parameters, continued, 1 definitions and settings, continued, Parameter oid description access type value – Alpha Technologies AlphaNet IDH4 for XM3-HP Series - Technical Manual User Manual
Page 80

80
746-257-B5-001, Rev. A1 (11/2013)
Parameter
OID
Description
Access
Type
Value
SYSTEM COUNTERS
atiBBSysViewCounters
1.3.6.1.4.1.926.1.4.1.1.4
Object Identifier
atiBBSysViewSelfTestInterval
1.3.6.1.4.1.926.1.4.1.1.4.1.0
Power supply Self Test interval
Read/Write
Integer
atiBBSysViewSelfTestCountdown
1.3.6.1.4.1.926.1.4.1.1.4.2.0
Power supply Self Test countdown
Read/Write
Integer
atiBBSysViewSelfTestDuration
1.3.6.1.4.1.926.1.4.1.1.4.3.0
Power supply Self Test duration
Read/Write
Integer
atiBBSysViewInverterRuntime
1.3.6.1.4.1.926.1.4.1.1.4.4.0
Power supply inverter runtime
Read Only
Integer
atiBBSysViewStandbyEvents
1.3.6.1.4.1.926.1.4.1.1.4.5.0
Power supply standby events
Read Only
Integer
atiBBSysViewRuntimeRemaining
1.3.6.1.4.1.926.1.4.1.1.4.6.0
Power supply runtime remaining
Read Only
Integer
atiBBSysViewTimeInStandby
1.3.6.1.4.1.926.1.4.1.1.4.7.0
Power supply time in standby
Read Only
Integer
atiBBSysViewTimeSinceLastStandby
1.3.6.1.4.1.926.1.4.1.1.4.8.0
Power supply time since last standby
Read Only
Integer
SYSTEM LOGS
atiBBSysLogs
1.3.6.1.4.1.926.1.4.1.2
Object Identifier
atiBBSysLogsEventsTable
1.3.6.1.4.1.926.1.4.1.2.1
Table of logged events
Read Only
atiBBSysLogsConfigTable
1.3.6.1.4.1.926.1.4.1.2.2
Table of logged configuration items
Read Only
atiBBSysLogsPerformTable
1.3.6.1.4.1.926.1.4.1.2.3
Table of logged performance information
Read Only
atiBBSysLogsBatteryTable
1.3.6.1.4.1.926.1.4.1.2.4
Table of logged battery information
Read Only
SYSTEM APPLICATIONS
atiBBSysApps
1.3.6.1.4.1.926.1.4.1.3
Object Identifier
atiBBSysAppsPsHealth
1.3.6.1.4.1.926.1.4.1.3.1
Object Identifier
atiBBSysAppsPsHealthPsCount
1.3.6.1.4.1.926.1.4.1.3.1.1.0
Indicates the number of power supplies that support
health analysis
Read Only
Integer
atiBBSysAppsPsHealthTable
1.3.6.1.4.1.926.1.4.1.3.1.2
Table - row for each power supply
atiBBSysAppsBattStatus
1.3.6.1.4.1.926.1.4.1.3.2
Object Identifier
atiBBSysAppsBattTable
1.3.6.1.4.1.926.1.4.1.3.2.1
Table - row for each battery
Read Only
Integer
atiBBSysAppsBattStringNum
1.3.6.1.4.1.926.1.4.1.3.2.1.1.1 String that this battery is a member of
Read Only
Integer
1 to 4
atiBBSysAppsBattBatteryNum
1.3.6.1.4.1.926.1.4.1.3.2.1.1.2 Battery number in string
Read Only
Integer
1 to 4
atiBBSysAppsBattMfgDate
1.3.6.1.4.1.926.1.4.1.3.2.1.1.3 Manufacture Date, typically stamped onto battery
Read/Write
Octet String
Date
atiBBSysAppsBattAge
1.3.6.1.4.1.926.1.4.1.3.2.1.1.4 Age of battery in months based on Manufacture
Date
Read Only
Integer
atiBBSysAppsBattMhos
1.3.6.1.4.1.926.1.4.1.3.2.1.1.5 Measured Battery MHOs
Read/Write
Integer
atiBBSysAppsBattBalancing
1.3.6.1.4.1.926.1.4.1.3.2.1.1.6 Status of attempt to balance the battery
Read Only
Integer
1=balanced
2=inProgess
3=failed
atiBBSysAppsBattStringCount
1.3.6.1.4.1.926.1.4.1.3.2.2.0
Indicates the number of Battery strings that support
Health Analysis
Read Only
Integer
atiBBSysAppsBattPerStringCount
1.3.6.1.4.1.926.1.4.1.3.2.3.0
Indicates the number of Batteries that support
Health Analysis
Read Only
Integer
atiBBSysAppsBattConductanceMeasurementDate 1.3.6.1.4.1.926.1.4.1.3.2.4.0
Date of last conductance measurement
Read Only
Octet String
Date and Time
atiBBSysAppsBattStandbyTimeRemaining
1.3.6.1.4.1.926.1.4.1.3.2.5.0
Remaining runtime if batteries are currently
discharging or available runtime for next discharge
Read Only
Integer
1=overThreeHr
2=twoToThreeHr
3=oneToTwoHr
4=lessThanOneHr
5=calculating
6=notAvailable
10.1 Definitions and Settings, continued