beautypg.com

0 battery sense wire kits, 1 36v single and dual strings, Fig. 8-1, 36v system, single string – Alpha Technologies AlphaNet IDH4 for XM3-HP Series - Technical Manual User Manual

Page 69: Fig. 8-2, 36v system, dual string

background image

69

746-257-B5-001, Rev. A1 (11/2013)

8.1

36V Single and Dual Strings

Fig. 8-1, 36V System, Single String

Sense Wire Kits:

Alpha P/N: 874-842-21 (6')

Alpha P/N: 874-842-27 (9')

Back of Plug

1

2

3

4

5

6

7

8

Vbatt 3A

[C] 36V

Pin 4

3A

POS

NEG

2A

POS

NEG

1A

POS

NEG

A/B [C/D] NEG

Pin 1

Vbatt 2A

[C] 24V

Pin 3

Vbatt 1A

[C] 12V

Pin 2

To Power Supply

Black

Red

Fig. 8-2, 36V System, Dual String

Sense Wire Kits:

Alpha P/N: 874-842-20 (6')

Alpha P/N: 874-842-28 (9')

POS

POS

POS

3B

NEG

2B

NEG

1B

NEG

1

2

3

4

5

6

7

8

Back of Plug

3A

POS

NEG

2A

POS

NEG

1A

POS

NEG

A/B [C/D] NEG

Pin 1

Vbatt 3A

[C] 36V

Pin 4

Vbatt 2A

[C] 24V

Pin 3

Vbatt 1A

[C] 12V

Pin 2

Vbatt 3B [D] 36V

Pin 7

Vbatt 2B [D] 24V

Pin 6

Vbatt 1B [D] 12V

Pin 5

To Power Supply

Red

Black

8.0 Battery Sense Wire Kits

Transponder Battery Sense Wire Kits are required for individual battery voltage monitoring when the XM3-

HP SAG option is NOT installed. For XM3-HP power supplies with the SAG option, it is recommended to

use the specific SAG wire kits for the SAG adapter kits to accommodate any existing transponder Battery

Sense Wire Kits. Otherwise, a SAG "No Harness" alarm will be generated if the Battery Sense Wire Kits

are connected to the transponder battery connections (A/B or C/D) instead of the SAG connector.