0 data management, continued – Alpha Technologies AlphaNet IDH4 for XM3-HP Series - Technical Manual User Manual
Page 48
48
746-257-B5-001, Rev. A1 (11/2013)
6.2.1 SCTE-HMS Configurable Alarms, continued
Table 6-3, Recommended Settings for IDH4 Series Analog Alarms
Analog Alarms and Common Settings
Analog Alarms
Description
Alarm
Enable LOLO
LO
HI HIHI Deadband
psTotalStringVoltage
36V
Scaled representation of the full
battery string in 1/100 Volts units
0x0F
3300
3500
4520 4570 50
psBatteryVoltage
Battery Voltage of individual
batteries, scaled 1/100 Volts units
0x0F
1050
1150
1530 1550 20
psInputVoltage
120V
Scaled representation of the input
line voltage in 1/100 Volts units
0x0F
Varies by site. The XM3-HP will switch to standby
at nominal +15% -20%
220V
0x0F
psOutputVoltage
60V
Scaled representation of the
power supply output voltage in
1/100 Volts units
0x0F
5650
6000
6600 7000 200
90V
0x0F
7800
8200
9150 9300 200
psPowerOut
Representation of power supply
output power in 1W units
0x00
It is recommended that psOutputCurrent be used
for output alarms.
psStringChargeCurrent
Battery string charge current,
scaled in 1/100 Amp units
0x0C
Disable Disable 1200 1250 20
psStringFloat
Battery string float charge current,
scaled in 1/100 Amp units
0x0C
Disable Disable 1200 1250 20
psOutputCurrent
15A
0x0C
Disable Disable 1650 1720 20
18A
0x0C
Disable Disable 1980 2060 20
22A
0x0C
Disable Disable 2420 2530 40
24A
0x0C
Disable Disable 2640 2750 40
psTemperature
-40 to +80 degrees C
0x0F
Varies by site
Alarms for Optional Generator
GenVBatIgnition
Scaled representation of the
generator's ignition battery in
1/100 Volts
0x0F
1150
1200
1500 1550 20
genEnclosureTemperature
Temperature inside generator's
enclosure in degrees C
0x09
-40
0
0
55
5
The following table displays the various analog alarms with common settings for the IDH4 Series
Transponder.
6.0 Data Management, continued