6.2.3 General Power Supply Alarms
The Intelligent CableUPS detects a wide array of alarms and displays the type of active alarm in the
Smart Display screen and the severity of alarm (e.g., Major/Minor) by means of the Inverter Module LEDs.
6.0 Data Management, continued
Active Alarm
Alarm type
Alarm Category
Probable Cause of Alarm
Corrective action
SELF TEST FAIL
Major
PWR
Output voltage failed or batteries less than
1.85V/C during Self Test.
1. Check Batteries
2. Check Inverter
LINE ISOLATION RELAY
Major
PWR
Line isolation has failed and Inverter
operations are suspended.
1. Replace Power Supply as soon as possble
OUTPUT FAIL
Major
PWR
The AC output has failed due to a bad Inverter
or transformer.
1. Check Configuration
2. Replace Inverter
3. Replace Power Supply
OUTPUT OVERLOAD
Major
PWR
The output is overloaded or shorted.
1. Remove Short Circuit
2. Reduce Output Load
3. Replace Power Supply
OUTPUT 1 TRIPPED
Major
PWR
Output 1 AlphaDOC hardware protection
mode is engaged and overloaded.
1. Reduce Output Load
2. Check AlphaDOC setting
OUTPUT 2 TRIPPED
Major
PWR
Output 2 AlphaDOC hardware protection
mode is engaged and overloaded.
1. Reduce Output Load
2. Check AlphaDOC Setting
CHARGER FAILURE
Major
PWR
Charger has failed to shut down; possible
battery over temperature condition exists.
1. Re-seat Inverter
2. Perform Self Test
3. Replace Inverter
INVERTER TEMP
Major
PWR
Inverter heat sink has exceeded set
temperature. (Stand-by operations suspended
until temperature drops to a safe level.)
1. Check Ventilation
2. Replace Inverter
CONFIG ERROR
Major
PWR
The power supply is improperly configured
and operation is suspended until error is
corrected.
1. Check Inverter Module
INPUT FAIL
Minor
PWR
Utility AC input has failed.
1. Check AC Input
2. Restore AC Input
3. Connect Generator
INPUT CURRENT LIMIT
Major
PWR
AC Input current exceeds threshold setting.
1. Reduce Output Load
2. Check Input Current Limit Setting
Table 6-6, Power Alarms: Classifications, Causes and Corrections
General power supply alarms are passed directly from the power supply to the transponder without
specific definition and are classified in the HMS MIB table as psMinorAlarm and psMajorAlarm. There
are a number of problems that can generate these alarms and the exact nature of the situation is not
specified. Minor and Major alarms are defined by the SCTE standards committee as follows:
psMajor
“Service has been dropped or a service interruption is imminent. Indicates that an immediate truck roll is
appropriate.” Several psMajor alarms are latching, meaning that the alarm won’t clear until the problem is
fixed and after a successful completion of a Self Test. A Self Test is the preferred method of verifying the
resolution of the alarm condition as cycling the power has the potential of masking the problem and not
indicating the actual state of the system.
psMinor
“A non-service affecting condition has occurred and should be monitored.”
The following table lists the psMajor and psMinor alarm definitions for the XM3-HP power supply.