0 alpha mib parameters, continued, 1 definitions and settings, continued, Parameter oid description access type value – Alpha Technologies AlphaNet IDH4 for XM3-HP Series - Technical Manual User Manual
Page 79

79
746-257-B5-001, Rev. A1 (11/2013)
Parameter
OID
Description
Access
Type
Value
ENVIRONMENTAL CONTROL CONNECTOR, continued
atiMgmtSysIOSysIOPinCtrl
1.3.6.1.4.1.926.1.3.2.8.20.0
Control of Output Pin
Read/Write
Integer
1=contactOpen
2=contactClosed
atiMgmtSysIOSysIOPinIn4
1.3.6.1.4.1.926.1.3.2.8.21.0
Status of Input Pin 4
Read Only
Integer
1=contactOpen
2=contactClosed
atiMgmtSysIOSysIOPinIn5
1.3.6.1.4.1.926.1.3.2.8.22.0
Status of Input Pin 5
Read Only
Integer
1=contactOpen
2=contactClosed
atiMgmtSysIOSysIOPinIn6
1.3.6.1.4.1.926.1.3.2.8.23.0
Status of Input Pin 6
Read Only
Integer
1=contactOpen
2=contactClosed
PLATFORMS
atiProductPlatforms
1.3.6.1.4.1.926.1.4
Object Identifier
atiBroadbandUPS
1.3.6.1.4.1.926.1.4.1
Object Identifier
atiBBSysView
1.3.6.1.4.1.926.1.4.1.1
Object Identifier
atiBBSysViewSelects
1.3.6.1.4.1.926.1.4.1.1.1
Object Identifier
atiBBSysViewSelfTestControl
1.3.6.1.4.1.926.1.4.1.1.1.1.0
Starts/Stops a system Self Test
Read/Write
Integer
1=Stop
2=Start
atiBBSysViewSelfTestInhibit
1.3.6.1.4.1.926.1.4.1.1.1.2.0
System Self Test is prevented. On reset, the IDH4
gets this value from the master XM3 (in a system
with more than one power supply).
Read/Write
Integer
1=Normal (default)
2=Inhibited
atiBBSysViewSystemControlMgr
1.3.6.1.4.1.926.1.4.1.1.1.3.0
If the System Control Manager is running, the Small
System Controller/Administrator (SSC or SSA)
is running and there is coordination between the
power supplies for charging, testing, etc. The value
of this item is stored in non-volatile memory.
Read/Write
Integer
1=Running
2=Disabled
atiBBSysViewFactoryDefaults
1.3.6.1.4.1.926.1.4.1.1.1.4.0
Will set all parameters back to the factory default
value
Read/Write
Integer
1=Normal
2=Reset
SYSTEM ALARMS
atiBBSysViewAlarms
1.3.6.1.4.1.926.1.4.1.1.2
Object Identifier
atiBBSysViewMajorAlarm
1.3.6.1.4.1.926.1.4.1.1.2.1.0
Indicates if any of the items monitored are in a major
alarm state
Read Only
Integer
1=OK
2=Alarm
atiBBSysViewMinorAlarm
1.3.6.1.4.1.926.1.4.1.1.2.2.0
Indicates if any of the items monitored are in a minor
alarm state
Read Only
Integer
1=OK
2=Alarm
atiBBSysViewSelfTestResult
1.3.6.1.4.1.926.1.4.1.1.2.3.0
If any of the items being monitored indicate that Self
Test failed, this item indicates a failure.
Read Only
Integer
1=OK
2=Fail
atiBBSysViewTempProbeStatus
1.3.6.1.4.1.926.1.4.1.1.2.4.0
If any of the devices being monitored indicate a
temp probe failure or absence, this item will alarm.
Read Only
Integer
1=OK
2=Missing
atiBBSysViewInputStatus
1.3.6.1.4.1.926.1.4.1.1.2.5.0
If ALL the items being monitored indicate no AC, this
item will alarm.
Read Only
Integer
1=OK
2=No AC Present
SCALARS
atiBBSysViewScalars
1.3.6.1.4.1.926.1.4.1.1.3
Object Identifier
atiBBSysViewInputVoltage
1.3.6.1.4.1.926.1.4.1.1.3.1.0
Power supply input voltage
Read Only
Integer
atiBBSysViewInputFrequency
1.3.6.1.4.1.926.1.4.1.1.3.2.0
Power supply input line frequency
Read Only
Integer
atiBBSysViewInputCurrent
1.3.6.1.4.1.926.1.4.1.1.3.3.0
Power supply input current
Read Only
Integer
atiBBSysViewBatteryVoltage
1.3.6.1.4.1.926.1.4.1.1.3.4.0
Battery voltage
Read Only
Integer
atiBBSysViewBatteryTemperature
1.3.6.1.4.1.926.1.4.1.1.3.5.0
Battery temperature (Degrees C)
Read Only
Integer
atiBBSysViewChargerCurrent
1.3.6.1.4.1.926.1.4.1.1.3.6.0
Sum of charging current from all power supplies
Read Only
Integer
atiBBSysViewChargerVoltsFloat
1.3.6.1.4.1.926.1.4.1.1.3.7.0
Battery charger float voltage
Read/Write
Integer
atiBBSysViewChargerVoltsEqualize
1.3.6.1.4.1.926.1.4.1.1.3.8.0
Battery charger equalization voltage
Read/Write
Integer
atiBBSysViewChargerVoltsTemperatureComp 1.3.6.1.4.1.926.1.4.1.1.3.9.0
Battery charger temperature compensation
(0 to 5mV/Cell/°C)
Read/Write
Integer
atiBBSysViewBatteryCapacity
1.3.6.1.4.1.926.1.4.1.1.3.10.0
Battery string capacity (Amp hours)
Read/Write
Integer
DETECT 6V BATTS
atiCibDiscTable
1.3.6.1.4.1.926.1.2.1.1.1.5.
14.0.11
Controls the ability to detect and report 6 Volt
batteries
Read/Write
Integer
0 = default
1 = Detect 6 Volt
Batteries
10.1 Definitions and Settings, continued
10.0 Alpha MIB Parameters, continued