Parameter

OID

Description

Access

Type

Value

ENVIRONMENTAL CONTROL CONNECTOR, continued
atiMgmtSysIOSysIOPinCtrl

1.3.6.1.4.1.926.1.3.2.8.20.0

Control of Output Pin

Read/Write

Integer

1=contactOpen

2=contactClosed

atiMgmtSysIOSysIOPinIn4

1.3.6.1.4.1.926.1.3.2.8.21.0

Status of Input Pin 4

Read Only

Integer

1=contactOpen

2=contactClosed

atiMgmtSysIOSysIOPinIn5

1.3.6.1.4.1.926.1.3.2.8.22.0

Status of Input Pin 5

Read Only

Integer

1=contactOpen

2=contactClosed

atiMgmtSysIOSysIOPinIn6

1.3.6.1.4.1.926.1.3.2.8.23.0

Status of Input Pin 6

Read Only

Integer

1=contactOpen

2=contactClosed

PLATFORMS
atiProductPlatforms

1.3.6.1.4.1.926.1.4

Object Identifier

atiBroadbandUPS

1.3.6.1.4.1.926.1.4.1

Object Identifier

atiBBSysView

1.3.6.1.4.1.926.1.4.1.1

Object Identifier

atiBBSysViewSelects

1.3.6.1.4.1.926.1.4.1.1.1

Object Identifier

atiBBSysViewSelfTestControl

1.3.6.1.4.1.926.1.4.1.1.1.1.0

Starts/Stops a system Self Test

Read/Write

Integer

1=Stop

2=Start

atiBBSysViewSelfTestInhibit

1.3.6.1.4.1.926.1.4.1.1.1.2.0

System Self Test is prevented. On reset, the IDH4

gets this value from the master XM3 (in a system

with more than one power supply).

Read/Write

Integer

1=Normal (default)

2=Inhibited

atiBBSysViewSystemControlMgr

1.3.6.1.4.1.926.1.4.1.1.1.3.0

If the System Control Manager is running, the Small

System Controller/Administrator (SSC or SSA)

is running and there is coordination between the

power supplies for charging, testing, etc. The value

of this item is stored in non-volatile memory.

Read/Write

Integer

1=Running

2=Disabled

atiBBSysViewFactoryDefaults

1.3.6.1.4.1.926.1.4.1.1.1.4.0

Will set all parameters back to the factory default

value

Read/Write

Integer

1=Normal

2=Reset

SYSTEM ALARMS
atiBBSysViewAlarms

1.3.6.1.4.1.926.1.4.1.1.2

Object Identifier

atiBBSysViewMajorAlarm

1.3.6.1.4.1.926.1.4.1.1.2.1.0

Indicates if any of the items monitored are in a major

alarm state

Read Only

Integer

1=OK

2=Alarm

atiBBSysViewMinorAlarm

1.3.6.1.4.1.926.1.4.1.1.2.2.0

Indicates if any of the items monitored are in a minor

alarm state

Read Only

Integer

1=OK

2=Alarm

atiBBSysViewSelfTestResult

1.3.6.1.4.1.926.1.4.1.1.2.3.0

If any of the items being monitored indicate that Self

Test failed, this item indicates a failure.

Read Only

Integer

1=OK

2=Fail

atiBBSysViewTempProbeStatus

1.3.6.1.4.1.926.1.4.1.1.2.4.0

If any of the devices being monitored indicate a

temp probe failure or absence, this item will alarm.

Read Only

Integer

1=OK

2=Missing

atiBBSysViewInputStatus

1.3.6.1.4.1.926.1.4.1.1.2.5.0

If ALL the items being monitored indicate no AC, this

item will alarm.

Read Only

Integer

1=OK

2=No AC Present

SCALARS
atiBBSysViewScalars

1.3.6.1.4.1.926.1.4.1.1.3

Object Identifier

atiBBSysViewInputVoltage

1.3.6.1.4.1.926.1.4.1.1.3.1.0

Power supply input voltage

Read Only

Integer

atiBBSysViewInputFrequency

1.3.6.1.4.1.926.1.4.1.1.3.2.0

Power supply input line frequency

Read Only

Integer

atiBBSysViewInputCurrent

1.3.6.1.4.1.926.1.4.1.1.3.3.0

Power supply input current

Read Only

Integer

atiBBSysViewBatteryVoltage

1.3.6.1.4.1.926.1.4.1.1.3.4.0

Battery voltage

Read Only

Integer

atiBBSysViewBatteryTemperature

1.3.6.1.4.1.926.1.4.1.1.3.5.0

Battery temperature (Degrees C)

Read Only

Integer

atiBBSysViewChargerCurrent

1.3.6.1.4.1.926.1.4.1.1.3.6.0

Sum of charging current from all power supplies

Read Only

Integer

atiBBSysViewChargerVoltsFloat

1.3.6.1.4.1.926.1.4.1.1.3.7.0

Battery charger float voltage

Read/Write

Integer

atiBBSysViewChargerVoltsEqualize

1.3.6.1.4.1.926.1.4.1.1.3.8.0

Battery charger equalization voltage

Read/Write

Integer

atiBBSysViewChargerVoltsTemperatureComp 1.3.6.1.4.1.926.1.4.1.1.3.9.0

Battery charger temperature compensation

(0 to 5mV/Cell/°C)

Read/Write

Integer

atiBBSysViewBatteryCapacity

1.3.6.1.4.1.926.1.4.1.1.3.10.0

Battery string capacity (Amp hours)

Read/Write

Integer

DETECT 6V BATTS
atiCibDiscTable

1.3.6.1.4.1.926.1.2.1.1.1.5.

14.0.11

Controls the ability to detect and report 6 Volt

batteries

Read/Write

Integer

0 = default
1 = Detect 6 Volt

Batteries