0 data management, continued, 4 battery alarms – Alpha Technologies AlphaNet IDH4 for XM3-HP Series - Technical Manual User Manual
Page 54

54
746-257-B5-001, Rev. A1 (11/2013)
Table 6-7, Battery Alarms: Classifications, Causes and Corrections
6.2.4 Battery Alarms
The Intelligent CableUPS detects a wide array of battery alarms and displays the type of active alarm in
the Smart Display screen and the severity of alarm (e.g., Major/Minor) by means of the Inverter Module
LEDs.
6.0 Data Management, continued
NOTE:
The cause of a psMajor or psMinor alarm can be determined by checking the Discretes table in the Alpha MIB
or by viewing the Web page. The cause will have the value of “ALARM.”
Active Alarm
Alarm type
Alarm Category Probable Cause of Alarm
Corrective action
Standby Disabled
NO BATTERIES
Major
BATT
Detected the absence of batteries (alarm inactive when
battery capacity or number of battery strings is set to 0).
1. Check Batt Breaker
2. Check Connections
3. Check Battery Fuse
YES
LOW BATT VOLTS
Major
BATT
Battery voltages below 1.833V/cell
1. Check AC Input
2. Restore AC Input
3. Connect Generator
NO
HIGH BATT VOLTS
Major
BATT
Battery voltages above 4.5V over target charger voltage
1. Check Batteries
2. Replace Inverter
NO
BATTERY EOD
Major
BATT
Batteries dropped below the low voltage shutdown level
1. Low Battery Disconnect
YES
BATTERY FAIL
Major
BATT
Charge current > 5.0A for 7 days while in float mode
1. Check Batteries
2. Replace Batteries
NO
BATT TEMP PROBE
Minor
BATT
Precision Temperature Sensor (PTS) failed or is not installed.
1. Check Connection
2. Replace Sensor
NO
REFRESH/BATT REFRESH ALARM
Minor
BATT
Battery Temperature Exceeded 60°C
1. Check Charger Settings
2. Check Batteries
3. Check Battery Temperature
NO
SAG OPTION
Minor
BATT
I2C has failed between XM3-HP and SAG
1. Check Ribbon Cable
2. Replace SAG
NO
SAG DELTA MEAN
Minor
BATT
Battery voltage is either too high or low from mean
1. Check Batteries
2. Replace Batteries
NO
SAG RELAY STUCK
Minor
BATT
Relay has stuck or 36V or 0V wire is no longer connected
1. Check SAG Bat
2. Check SAG Wires Unit
3. Replace SAG
NO
STR X MISWIRED
Minor
BATT
Battery wires are not connected properly
1. Check SAG Wires Bat
2. Check SAG Wires Unit
3. Replace SAG Wires
NO
SAG NOT CALIBRAT
Minor
BATT
Calibration data is not or is no longer available
1. Replace SAG
NO
X BAL STAGE
Minor
BATT
Stage 0 and 1 are normal. Stage 2 shows that the batteries
are not of similar capacity. Stage 3-5 trigger check battery
alarm to show that there is a major capacity imbalance
1. Check Batteries
2. Replace Batteries
NO
SAG NO HARNESS
Minor
BATT
Battery wires are not connected properly
1. Check SAG Wires Bat
2. Check SAG Wires Unit
3. Replace SAG Wires
NO
NOTE:
When in alarm, the IDH4
General and Advanced Power Supply Web pages will display the cause of active
power supply alarms next to the parameters
Major Alarm and Minor Alarm.
Fig. 6-3, IDH4 Series Alarms on General Web Page